Page 191 - Hydrogeology Principles and Practice
P. 191

HYDC05  12/5/05  5:35 PM  Page 174






                 174    Chapter Five


                 be monitored in one or more observation wells in
                 close proximity to the pumped well (Fig. 5.31a). The
                 constant discharge test programme has three parts:
                 pre-test observations; pumping test; and observations
                 during potentiometric recovery after the pumping
                 has stopped. Prior to the start of the test, the initial
                 water levels relative to a local datum must be meas-
                 ured and monitored for effects external to the pump-
                 ing test, for example tidal fluctuations and barometric
                 variations (Section 5.2), and the details of the site
                 hydrogeology recorded, for example well depths
                 and diameters, strata penetrated and the location
                 of nearby streams that could act as recharge bound-
                 aries. From the start of the test, the pumping rate
                 is monitored and paired values of drawdown and
                 time are measured in the pumped and observation
                 wells at specific time intervals that increase as the
                 test progresses (Fig. 5.31b). Initially, the cone of
                 depression expands rapidly but the expansion slows
                 logarithmically with time as the volume of aquifer
                 contributing to the pumped well increases. Hence,
                 the measurement time interval can also increase
                                                             Fig. 5.31 (a) Suggested cruciform borehole array and (b)
                 approximately logarithmically as the cone of depres-
                                                             diagrammatic representation of the drawdown response in an
                 sion grows. Eventually, a state of quasi- or actual
                                                             observation well for a constant discharge test followed by a
                 equilibrium conditions may be reached, when the  recovery test. By siting observation boreholes along two radii at
                 rate of recharge to the borehole catchment balances  right angles to each other, this enables the aquifer characteristics
                 the rate of abstraction.                    to be measured and an indication of aquifer geometry and
                                                             anisotropy to be obtained (Toynton 1983). As a minimum, there
                   The last stage of the constant discharge test is the
                                                             should be at least one observation borehole in order to obtain
                 recovery phase after the pump has been switched off.
                                                             reliable pumping test data. The recommended minimum period
                 On cessation of pumping, groundwater levels will  of a constant discharge test where observation wells are more than
                 recover to a static water level following a drawdown  100 m from the pumped well, or in an unconfined aquifer where
                 versus time curve that is approximately the converse  response time is slow, is 3 days. A 5-day test may be advised in
                                                             situations where derogation effects on neighbouring wells need
                 of the drawdown curve (Fig. 5.31b). The ground-
                                                             to be measured. Constant discharge tests involving more than one
                 water levels should be measured from the time the
                                                             pumping well (a group test) are used to test wide areas of aquifer
                 pump is switched off with a similar, logarithmically  and require extended periods of pumping (Clark 1988).
                 increasing time interval as in the pumping test. In
                 theory, the length of the recovery test is the same as
                 the pumping test but, in practice, the recovery is
                 monitored until the water level is within about 10 cm  results. To avoid this problem, the pumped water
                 of the original static water level (Clark 1988).  should be abstracted to a point beyond the range of
                   For further details on the requirements of a pump-  influence of the test. The following sections provide
                 ing test, the reader is referred to the code of practice  a description of the common methods of pumping
                 produced by the British Standards Institution (BSI  test analysis that are applied to confined aquifers
                 1992) and the procedures given by Walton (1987),  and, where conditions allow, unconfined aquifers.
                 Clark (1988) and Brassington (1998). One important  For a fuller treatment of the various solutions and
                 consideration is the disposal of the discharged water.  techniques for more complex aquifer conditions,
                 In tests of shallow aquifers, this water may infiltrate  the reader is directed to the specialist handbook of
                 back into the aquifer and interfere with the test  Kruseman and de Ridder (1990).
   186   187   188   189   190   191   192   193   194   195   196