Page 158 - Industrial Power Engineering and Applications Handbook
P. 158

6/138  Industrial Power Engineering and Applications Handbook
                                                               Pump head




















                             0                 4                4
                                                Capacity 'Q'-
                           (a) Discharge versus suction head




















                                                  Capacity 'Q' -
                             0                 4                4               Q,

                            (b) Discharge versus pump power

                         Figure 6.41  Power saving with the use of  static control compared to throttle control





         Considering the efficiency of  slip  recovery system as  95%   6.16  Application of static drives
         and 300 operating days in a year, the power feedback to the
          main supply source through the slip recovery system in 20%
         of the time,                                   6.16.1  Soft starting (Vlf control)
                 = [0.95 x 791 . [0.2 x 300 x 241       This facilitates a stepless reduced voltage start and smooth
                 = 108 072 kWh                          acceleration  through  control of the  stator  voltage. The
                                                        smooth  voltage  control  limits  the  starting torque  (T,J
         And in terms of costs at a tariff  rate of Rs 1.2 per unit,   and also the starting inrush current (IJ  a5 illustrated in
                 = RS 1.2 x 108 072                     Figure 6.43. This is achieved by  arranging  a full-wave
                                                        phase-controlled circuit by connecting two SCRs in anti-
                 = Rs 129 686.4 per year                parallel or a triac in each phase as illustrated in Figure