Page 153 - Industrial Power Engineering and Applications Handbook
P. 153

Static controls and braking of motors  6/133
           where  C is  the  capacitance  used  across the  device.   filter circuits may be provided  on the incoming  side
           During a turn OFF operation the stored energy, Q, of   for more  prominent  harmonics.  (For details of  filter
           the circuit will discharge into this capacitor and charge   circuits  see  Section  23.9.) The  main  purpose  of
           the same to its optimum level (charging time constant   inductance here is protection. rather than suppression
           r= R C) and slow down the rate of rise of TRV (r.r.r.v.).   of  harmonics.
           i.c. duldt across the static circuit and limit the voltage   Due to a high time constant of the dampening circuit
           spikes. similar to motor protection discussed in Section   t = L,/R (R being the resistance of the circuit) it will
           17. IO. 1.  The higher the value of  C, the lower will  be   also delay occurrence of the fault by  which time the
           the voltage (commutation) overshoots. During a switch   circuit’s protective scheme may initiate operation.
           ON the capacitor discharges its total energy into the R   It would also add to the line impedance to contain
           and  prepares  for the  next  switching operation.  The   the severity of the fault conditions.
           power dissipation into R is proportional to the switching   From the above we notice that the current surges
           frequency. R also limits the peak value of the discharge   can be caused either by the tripping of a current limiting
           current  through  the  static  device  and  damps  the   device.  when  the  distribution  is  through  a  large
           oscillations.  Here the use of  C is to hold the charge   transformer on which is connected the static circuits.
           and then release the same into R and not to smooth the   or by switching of the SCRs within the converter circuit
           ripples.                                       itself. The protective scheme for both remains the same
           Ciirrerlr rrnrisirrits  A similar situation will arise when   and is  located at the incoming of the semiconductor
           a switching ON operation of the rectifier unit  occurs   circuits. There can be two situations. When  the static
           when  it is a thyristor rectifier.  Under load conditions.   circuits are being fed through a dedicated transformer
           the  stored  magnetic  energy  in  the  incoming  supply   in  all  probability  no  additional  inductor  will  be
           system. which can be the feeding transformer and the   ary. Not even when there is a large transformer
           line reactances similar to a fault condition discussed   g  a  large  distribution  network  on  which  is
           earlier.  may  cause  a  current transient  which  can  be   connected the semiconductor circuits. It  is. however.
           expressed by                                   better to carry out the trapped energy calculations to
                                                          compare these  with the inductance already available
                                                          in the switching circuits of the semiconductor devices.
                                                            When there is no dedicated transformer and these
                                                          circuits  are  connected on the  system  bus  directly  a
           where                                          large inductor will be essential at the incoming of the
               V =applied voltage                         static circuits, sufficient to absorb the trapped charge
              L  = inductance  of the total circuit up to the d.c.   within the transformer and the interconnecting cables
                  link and                                up to the converter unit. The size of the inductor can
            di/d/ = rate  of  change  of  current,  as the  switching   be  calculated  depending  on  the  size  (kVA) of  the
                  ON is a transient condition and causes overload   distribution  transformer,  its  fault  level  and  the
                  and  short-circuits. This  is  rnaxirnurn  at  the   characteristics of its current limiting protective device.
                  commencement of switching ON and becomes   An inductor  sufficient to absorb  i,:  . L  of the  trans-
                  zero  on  its  completion.  It  is  analogous  to   former and the cables may be provided at the incoming
                  contact  making  in  an  interrupter  (Section   of the static circuits.
                  19.1. I).  The same situation  will  arise even
                  during  a  fault  condition.  Excessive  rate  of   Voltage surges in the inverter circuit
                  change of current may cause an overload and
                  even a short-circuit.                 Generally, voltage surges on an  LT  system are of little
                                                        relevance as analysed  in Section  17.7.6. Instances can.
           The rate of current change must therefore be controlled   however, be cited of motor insulation failures, even on
           to a safe limit by providing a dampening circuit on the   an LT  system, when the machine was being controlled
           supply side. This can be a series inductance as shown   through a static drive, which might be an IGBT switched
           in Figures 6.2h(a), 6.34 and 6.36. This inductance may   or a thyristor (GTO) switched inverter. the reason being
           not be necessary when the unit is being supplied through   a  steep  rising  switching  wave  generated  through  the
           a dedicated transformer. The inductor will absorb the   inverter circuit. The output of the inverter unit being in
           magnetic charge and damp the rate of rise of current.   the shape of a non-sinusoidal  voltage waveform also adds
                                                        to the  switching transients. To  visualize the effects of
                     di                                 fast switching in a static circuit, it is relevant to corroborate
           NOW  V = L  -
                     dt                                 these with the switching of a conventional HT interrupting
                                                        device, discussed in Section 17.7. The static devices also
           L, is  the  additional  series  rcactmce. The higher  the   cause switching surges and their severity is also defined
           value of L,, the lower will be the rate of rise of current.   by their amplitude and the rise time (Figure 17.2). These
             The inductor on the input side also  suppresses the   devices  are  seen  to  produce  voltage  surges  with  an
           harmonics  in  the  incoming  supply,  as  high  Li will   amplitude up to two to three times the voltage of the d.c.
           providc  a high  impedance path  to higher harmonics.   link and a rise time as low as 0.05-0.4  ps (typically) in
           For suppression of harmonics, where the supply system   IGBTs and 2 to 4 ps (typically) in GTOs (see Lawrence
           is  already  substantially distorted,  additional  L-C   et al. (1996) and  the  Further reading  at the  end  of  the
   148   149   150   151   152   153   154   155   156   157   158