Page 150 - Industrial Power Engineering and Applications Handbook
P. 150

6/130 Industrial Power Engineering and Applications  Handbook
        capacitive switching (Section  17.7). They also produce   A high value of L will  limit the rate of rise of  fault
        harmonics. However, a power diode converter unit having   current  for  the  same  voltage  and  save  the  circuit
        no switching sequence is devoid of such a phenomenon.   components.
        A thyristor  (SCR) switched phase-controlled  converter   2  A  low  dildt  will  also  help  to  smooth  the  d.c.  link
        unit produces large quantities of harmonics on the supply   current waveform.
        (a.c.) side and also in the d.c. link and also voltage and   3  It  has a disadvantage  in that it may have a sluggish
        current surges on the incoming supply  side. An  IGBT,   response  to  the  control  circuit  demands  due to  its
        on the other hand, as used in an inverter circuit, causes   high time constant (z = L/R)
        only  moderate  harmonics  during  switching,  but  does
        produce voltage surges on the load side. All these factors   Current harmonics on the incoming
        are not desirable and must he suppressed or tamed at the   ax. supply side
        point  of  occurrence  to  save  the  connected  equipment
        and the  devices. Below  we  discuss these  phenomena,   The presence  of  harmonic  quantities  in  the  electronic
        particularly  for  thyristor  circuits  and  their  possible   circuit distorts the sinusoidal incoming supply system to
        remedies.                                     a non-sinusoidal one the magnitude of which will depend
                                                      upon  the configuration  of  the converter circuit and the
        6.13.1  Suppressing the harmonics (in phase-   variation in the connected load. The line side converter
              controlled rectifier units)             unit draws a somewhat squarish waveform current from
                                                      the mains, as analysed in Figure 23.7.  It may adversely
        Phase-controlled rectifier circuits generate excessive odd   influence the power equipment operating on the incoming
        harmonics such as 5th, 7th,  llth,  13th etc.,  depending   supply  side  of  the  system,  which  may  be  a  motor,  a
        upon the  pulse  number, n, of  the circuit  configuration   transformer or a generator, due to higher no-load losses
        adopted, as discussed in Section 23.6(h). These harmonics   as a consequence of high harmonic frequencies (equations
        add to the inductive loading of the circuit since XL 0~ fh   (1.12) and (1.13)). It may also cause overloading of the
        and diminish the p.f. of the system, although they hardly   capacitor  banks  connected  on  the  incoming  side  and
        influence an induction  motor,  (Section 23.5.2(B)). The   subject all this equipment to higher voltage stresses. The
        3rd harmonic3 are totally absent because mostly six pulse   higher inductive loading also diminishes the p.f. of the
        thyristor converters are employed, which  eliminate all   system. To contain the  influence of  these  features, the
        the 3rd harmonics from the voltage and the current output   use of filter circuits to suppress the harmonics and power
        waveforms. Thyristors  in  other configurations  such as   capacitors, to improve the system p.f. on the incoming
        12, 18 and 24 pulses are also possible, which can eliminate   side are mandatory to maintain a healthy supply system,
        most of the harmonics from the output waveforms. The   particularly  when  it  is feeding  a  few  phase-controlled
        higher  the  pulse  number,  the  closer  it  approaches  the   converter units, handling large machines and generating
        mean and effective (r.m.s.) values of the rectified voltage   high harmonics. Figure 6.34 shows the use of an inductor
        and the voltage approaches a near peak  value (Section   in  the  incoming circuit to  suppress the harmonics  and
        23.6(b)). (See also Figure 23.10.) However, higher pulse   limit current overshoots. Power capacitors are not shown,
        thyristor  converters  become  very  expensive and  are   which can be provided for the whole system at a centralized
        employed only for very large power applications.   location.  The  design  of  filter  circuits  and  the  size  of
                                                       power capacitors, to adopt a more appropriate corrective
        Current harmonics in a d.c. link               method,  will  require a  meticulous  network  analysis to
                                                       determine the  actual numbers  and magnitudes  of  such
        To limit the current harmonics generated in the d.c. link,   harmonics  present  in  the  system. The  subject  is  dealt
        series smoothing reactors are inserted on the d.c. side as   with in more detail in Section 23.5.2. In Figure 6.24(a)
        shown in  Figure 6.24(a). They  are large  iron core un-   we have shown a few more common types of thyristor
        saturable reactors (L). (For details on reactors see Chapter   configurations, their voltage and current wave-forms and
        27.) They provide high impedance paths to the different   the application of reactors to suppress the harmonics and
        harmonic  quantities  and  suppress  the  more  prominent   smooth ax. ripples.
        of  these  at the source,  and provide  a near  smooth d.c.
        output voltage waveform. For large power applications,
        requiring a near-constant d.c. output, more accurate L-C
        circuits  (even more than  one) may  be  provided  in  the   6.14  Protection of semiconductor
        d.c. link to suppress the more prominent of the harmonic   devices and motors
        quantities.
          A large  inductor  in  the  d.c.  link  may  also  play  the   6.14.1  Overvoltages and voltage surges caused
        following roles:                                     by disturbances in an LT system

        I  In the event of a fault in the d.c. link it will add to the   Semiconductor devices are irreparable after a failure and
          circuit  impedance and limit the rate of  rise of  fault   hence  require  extra  precautions  for  their  protection.
           current, since under a transient condition   Although a voltage transient generally is a phenomenon
                                                       of  HT  systems, as discussed  in  Chapter  17, moderate
                di                                     long-duration  switching  surges  (voltage spikes),  other
           v= L-
                dt                                     than  lightning and the transference of surges, are noted
   145   146   147   148   149   150   151   152   153   154   155