Page 170 - Industrial Power Engineering and Applications Handbook
P. 170

6/150  Industrial Power Engineering and Applications Handbook

         Features            A.C. drive                Variable Speed fluid coupling   D.C. drive
         21  Harmonics       They generate high harmonics nk ?  There arises no such   Higher than even a.c. drives,
                              1  (Section  23.6(b)) and  must  be  phenomenon   because of commutator arcing
                             suppressed by  using filter circuits            which it produces  at high
                                                                             frequencies
         22  Unfriendly environmental  Not suitable. The static controls must  No problems  as it is a sealed   Not suitable at all, as the motor
            conditions such as   be located away from such areas in  unit. But for controls which   itself cannot be relocated in
            dustladen  areas, fire   well-protected  rooms   may be located separately   safer areas
            hazardous, corrosive and
            contaminated locations
         23  Heating          (i)  Moderate in transistor  controls  Very high at lower speeds and   Moderate
                                but                   requires extensive cooling
                              (ii)  Excessive in thyristor
                                controls. The higher the rating
                                the higher the temperature
                                rise. They require extensive
                                cooling arrangements which
                                may be external or forced

         24  Maintenance and   May be high. For efficient   Very low maintenance. Where a  Downtime due to brushes is
            downtime          maintenance  high-skilled  operators  mechanical ruggedness  is   about  1 hour only in 6 months’
                              and their proper training are essential,  required, a fluid coupling   to a year’s time. However,
                              besides stocking enough spares as   provides  a more reliable   meticulous  monitoring of
                              recommended by the manufacturer.  solution     brushes  and commutator
                              Yet the expert services of the                 condition  is important and so
                              manufacturer  may sometimes be                 also the environmental
                              necessary. At times, the spares may            conditions. Controls will also
                              not be readily available or it may             need similar attention as for
                              not be possible to repair them                 ax. drives. In a breakdown, the
                              immediately. In such cases either it           motor cannot be run in any way
                              is a total shutdown or the controls            (unlike ax. motors) and would
                              have to be bypassed and the machine            lead to a total shutdown
                              run on DOL
         __                              _.            -~
         25  Cost consideration   A costly arrangement   It is generally  cheaper than a   Quite economical compared to
                                                       static drive in all ranges   an a.c. drive. The following
                                                                             may give a rough idea:
                                                                              Up to  10 kW - price difference
                                                                             not significant
                                                                             Above 10-40  kW-  a.c controls
                                                                              may be costlier by 3MO%
                                                                              Above 40-130  kW - a.c.
                                                                              controls may be costlier by
                                                                              40-50%
                                                                              In the range of 500 kW and
                                                                              above - a.c. controls may be
                                                                              costlier bv 2.5 to 3 times and
                                                                              even more in still higher ranges