Page 174 - Industrial Power Engineering and Applications Handbook
P. 174

6/154  Industrial Power Engtneering and Applications Handbook
         the braking torque curve will almost take the shape of   for a particular configuration, as indicated in
         the motor's normal speed-torque  curve.              Figure 6.57, To avoid overheating and excessive
           If an independent d.c. source is not available a single-   electromagnetic forces,  i&  is  normally not
         phase transformer and a rectifier bridge as shown in   allowed to exceed ZaW)
         Figure 6.58 can also be used to obtain the required   Te =  average load torque between the running speed
         d.c. voltage. Although the requirement of d.c. excitation   and the final speed {Figure  6.59)
         voltage is not high, the rating of the rectifier transformex   Tb =  average braking torque between the running
         and the bridge should  be commensurate with the braking   speed and the final speed (Figure 6.59). This
         force required. This braking force would depend upon   will depend upon the braking duty the motor
         the size of  the motor and the time of braking. If  the   is required to perform such as the final speed,
         braking current, idcr is known, which is a measure of   Nrl (which we have considered as zero in Figure
         the braking torque necessary to fulfil a particular load   6.541, and the duration within which the motor
         duty  requirement,  the  excitation  voltage  e  can  be   must brake to this speed from N,. This can be
         determined for  different winding  configurations, as   determined from equation (4.8)
         indicated in Figure 6.57. The ik can be determined   T,  = braking torque of the external brakes, if provided
         from  the following  equation,  considering the  same   otherwise it may be. considered to be zero
         ampere turns as for a standard motor:           T,, = locked rotor (starting) torque of the motor
                                                         ka = a factor to account for the average braking torque.
                                              (4.1 1)        This may be considered to be  1.3-1.7 (consult
                                                             the manufacturer for a more accurate value)
                                                         In addition to electrical br  ng, a mechanical brake,
         where                                           as discussed in Section 6.20.1(A) may also be essential
          z&  =  braking current                         if  the  motor  is required  to  be  stopped completely
        Ist(phl =  phase value of the starting current   because, at any value of excitation current, the motor
                                                         will never reach a standstill condition, The heat of
            = I, (for a delta-connected stator or rotor)
              4-3                                        braking up to the standstill condition {Nrl= 0) is roughly
           kl =  factor to determine the equivalent ampere turns   equal to one start and is expressed by equation (6.9).
                                                      2  Plugging  By  changing any two of  the phases the
                                                         motor will develop a torque in the reverse direction
                                                         and provide the necessary braking. The voltage across
         -  v



























                                                                           Spsed -

               I  l  l                                                                        I
               $  1  8
                                                                Totel braking torque at point A = Te + Tb

       Figure 6.58  Obtaining d.c. voltage through a bridge rectifier   Figure 6.59  Braking torque during d.c. electric braking
   169   170   171   172   173   174   175   176   177   178   179