Page 328 - Industrial Power Engineering and Applications Handbook
P. 328

Protection of  electric motors la307
      Table 12.2  Characteristics of  a Pt - 100 RTD

      Temperature                Resistance
      eoc                        a
        0                        100                                              Conductor of
       50                        119.40                                           top coil side
      100                        138.50
      110                        142.28
      115                        144.18
      120                        146.06                     RTD or -,
      125                        147.94                   thermo-couple
      130                        149.82                                           Conductor of
      135                        151.70                                        /-bottom  coil side
      140                        153.57
      145                        155.45
      150                        157.32
      Source  IEC 60751
                                                     Figure 12.42  Location of a RTD or thermo-couple in a motor
                                                     winding
         160
                                                       their  simple wiring. They are generally  preferred  to
                                                       thermistors for large LT and all HT motors.
         150
                                                     12.8.2 Bearing temperature detection
                                                           (by PTC thermistors or RTDs)
                                                     Motors  are  also  recommended  to  have  one  bearing
       -                                             temperature detector in each bearing. This can be fitted
       t  140
       c:
                                                     within the threaded walls of the bearing that reach up to
         130                                         the bottom of  the bearing shell, i.e. close to where the
       C                                             heat  is produced.  Each detector  may  have two sets of
       2                                             contacts, each having  ‘2-NO’ contacts, rated for 5 A at
       .Y
                                                     240 V a.c. and 0.5 A at 220 V d.c. One set can be set at
       i?  120
                                                     a lower value to provide an audio-visual alarm and the
                                                     other at a higher value to trip the motor.
         110                                         12.8.3 Coolant circuit water pressure and
                                                           temperature (moisture) detection
                                                     Water-cooled  motors,  type CACW (cooling type ICW
         100
           0     25    50    75    100   125   150   37 A  81  or  ICW  37A  91)  (Section  1.16, Table  1.12)
                         Temp (0)OC-                 should be  fitted with  moisture detectors  to provide  an
                                                     audio-visual alarm in the event of a leakage in the water
      Figure 12.41  Characteristic of a Pt -100  resistance temperature   circuit or a higher coolant temperature.
      detector (RTD)
                                                     12.8.4 Detection of moisture condensation in the
                                                           windings (by space heaters)
        PTC thermistors  These are fragile and require usable
        space  in  the  slots.  They  are  normally  fitted  in  the   Motors  generally  above  37.5  kW  located  in  a  humid
        overhangs of the stator windings, as shown in Figure   atmosphere or required to be stored idle for long periods
        12.39(a). A sudden problem with the motor, causing   may be provided with one or two and even more space
        overheating,  is instantly detected by  an audio-visual   heaters, depending upon the size of the motor, suitable
        alarm or a trip. They are preferred for smaller motors.   for 240 V, 1-$I a.c. supply, to maintain the motor’s internal
        For  larger  motors,  protection  through  monitoring  is   temperature  slightly  above  the  dew  point  to  prevent
        preferred to sensing only. Monitoring is possible through   moisture condensation or deterioration of the insulation
        RTDs or thermocouples.                       during  a shutdown. The heaters  are located  inside  the
        RTDs or thermocouples  These are normally embedded   motor  at  the  lower  end  of  the  stator  so that  they  are
        in the stator windings  as illustrated  in Figures  12.42   easily  accessible  and  their  removal  and  replacement
        and  12.39(a). The winding  temperature  can  now  be   presents no problem. The rating of  total heating power
        monitored  continually  and  a  temperature  replica  of   may vary from about 100 watts to 3500 watts, depending
        the machine obtained at any time. Figure 12.39(b) shows   upon the size of the motor. For motors up to 400 kW, one
   323   324   325   326   327   328   329   330   331   332   333