Page 410 - Industrial Power Engineering and Applications Handbook
P. 410

13/384  Industrial Power Engineering and Applications Handbook





                                                                                           IIC-I
                                                                                            (52i)


                                                                                           (52iii)











                                                                                             I
                                                                                         (52ii) I  I
                                                                                             I
                                                                                             I
                                                                                             I
                                                                                         (52ii)  I
                                                                                             I
                                                                                             I

                   .                                                   .

                              IIC-I                    BIC                       IIC-2
                              (52i)                    (52iii)                   (52ii)
                  Figure 13.46  Control scheme for two electrically operated sources of supplies and a bus coupler


       that  of  an  HT  switchgear  assembly. Moreover, HT   directly, but this will be found to be more cumbersome
       assemblies above 33 kV are generally the outdoor type   and time-consuming.
       and installed in the open. The discussions above have   2  While putting into service
       therefore laid greater emphasis on the features of an LT   One may follow field tests as discussed in Section
       switchgear assembly. The features for an HT assembly   14.5 before putting the switchgear or the controlgear
       up  to 33 kV  are not  very  different except for thicker   assembly into service.
       enclosure and heavier load-bearing members, to carry   If  the insulation resistance is observed to be low
       larger HT  equipment (interrupting devices, CTs, PTs,   the interior of  the  switchgear or  the controlgear
       insulators etc.). The clearances and creepage distances   assembly should be dried out to attain the required
       will  also be  greater, according to  the  system voltage   value before energizing it. The procedure to dry
       (Section 28.5.2).  For more details refer to IEC 60298,   the moisture is similar to that for motors and is
       IEC 60694 and ANSI-C-37/20C.                       discussed in Section 9.5.2. In this case during the
                                                          heating-up period the insulation resistance may first
                                                          drop and reach its minimum, stabilize at that level
       13.9 General guidelines during                     and then start to rise gradually. Continue the process
             installation and maintenance of              until it reaches its required level as shown in Table
                                                          14.7.
             a switchgear or a controlgear                In HT switchgear assemblies provide a surge arrester
             assembly                                     or a  lightning arrester, wherever necessary. Also
                                                          refer to Section 17.11.
       1  Installation  and fixing  The assembly  should be   It is advisable that all the protective devices provided
         installed in a room that is well ventilated (except for   in the assembly be set to their minimum values to
         outdoor  assemblies), on  a  rigid  concrete or  steel   ensure fast tripping. They can be adjusted for proper
         foundation to eliminate vibrations. A simple and more   settings when putting the assembly into service.
         common  practice  of  fastening on  a  separate steel   3  Maintenance of busbars and busbar connections
         foundation frame is illustrated in Figure 13.48. The   All the joints, particularly power joints at the main
         assembly may also be fixed on a concrete foundation   busbars, tap-offs and cable ends, should be checked
   405   406   407   408   409   410   411   412   413   414   415