Page 789 - Industrial Power Engineering and Applications Handbook
P. 789

Power capacitors: behaviour, switching and improvement of  power factor  23/745

          load,  and  hence  further  distort  an  already  distorted   source reactance, an inductor equivalent to 6% value of
          voltage waveform.                           the capacitive reactance can be  provided  in  series with
          Harmonics will  mean                        the shunt capacitors.
          - Higher voltage and current than apparent    If  there  are  many  large  or  small  consumers  that  a
          - Adding to line loading and losses, and    distribution line is feeding, it is possible that the voltage
          ~  Reducing the actual load p.f.            of the network may be distorted beyond acceptable limits.
          Harmonic  effects  are  reduced  by  the  use  of  shunt   In  this case it is advisable to suppress these harmonics
          capacitors installed to improve the p.f. of the system   from the system before they damage the loads connected
          or  an  individual  load,  as  they  provide  a  very  low   in  the  system.  Preferable  locations  where  the  series
          impedance  path  to  harmonic  quantities  and  absorb   inductor or the filter-circuits can be installed are:
          them. But using shunt capacitors alone is not sufficient
          as  at  certain  harmonic  frequencies,  the  capacitive
          reactance  of  these  capacitors,  along  with  leakage   1  At  the supply end and/or
          capacitance C,, of the line, if it is an HV or EHV line   2  At the receiving end of the consumer. using power at
          (Table 24.l(b)) may tune up  with the  line inductive   HT and generating high harmonics (e.g. rolling mills,
                                                         induction  and  arc  furnaces,  electrolysis  plants,
          reactance L and cause a series or parallel resonance
          and develop high voltages. This phenomenon will be   chemicals and paper mills). Electricity companies will
                                                         always prefer the consumers to suppress the harmonics
          more apparent  on  an  HV  and EHV  system  than  an
                                                         at their end. Even if this practice is adopted by some.
          LT  system. On LT  systems, the line resistance itself   small harmonics generated by many small consumers,
          is enough to provide an in-built dampening effect to   who may not take any preventive steps to contain the
          a  possible  resonance  (z  =  R,)  at  least).  To  avoid   harmonics generated by their plant, may still exist in
          resonance, filter-circuits are used. Filter-circuits may   the system. As a result, the distribution network may
          bc tuned for the lowest harmonic content or for each   contain some harmonics which affect the performance
          harmonic  separately  as  discussed  later,  when  the   of other loads in the system. If the level of harmonics
          system is required to be as near to sinusoidal waveform   is unacceptably high (Tables 23.2 and 23.3) they must
          as  possible.  The  system  may  contain  second, third   be  suppressed at the supply end.
          and fifth and higher harmonics, but it may be sufficient
          to tune it to just below the fifth harmonic, which will
          be able to suppress most of the other harmonics also
          to a great extent. as it will make the circuit inductive   23.9  Filter circuits:  suppressing
          for all harmonics.                                harmonics in a power network

          In an  HT system, either the star is not grounded or it   The use  of  a reactor  in  series  with  the  capacitors  will
        is a delta-connected system and hence the third harmonic   reduce the harmonic effects in a power network, as well
        is mostly absent, while the content of the second harmonic   as their effect on other circuits in the vicinity,  such as a
        may  be  too  small  to  be  of  any  significance.  For  this   telecommunication network (see also Section 23.1 I  and
        purpose, where harmonic analysis is not possible, or for   Example 23.4). The choice of reactance should be  such
        a new installation where the content of harmonics is not   that it will provide the required detuning by  resonating
        known, it is common practice to use a series reactor of   below the required harmonic, to provide a least impedance
        6% of the reactive value of the capacitors installed. This   path  for that harmonic and filter it out from the circuit.
        will suppress most of the harmonics by making the circuit   The basic idea of a filter circuit is to make it respond to
        inductive, up to almost the fourth harmonic, as derived   the current of one frequency and reject all other frequency
        subsequently.  Where,  however,  second  harmonics  are   components. At  power frequency, the circuit should act
        significant, the circuit may be tuned for just below  the   as a capacitive load and improve the p.f. of the system.
        second harmonic. To arrive at a more accurate choice of   For the fifth harmonic, for instance,  it  should resonate
        filters, it is better to conduct a harmonic analysis of the   below 5 x 50 Hz for a 50 Hz system, say at around 200-
        system  through  a  harmonic  analyser  and  ascertain  the   220 Hz, to avoid excessive charging voltages which may
        actual harmonic quantities and their magnitudes present   lead  to
        in  the  system, and  provide  a correct series  or parallel
        filter-circuits for each harmonic.
          As noted from general experience, except for specific   0  Overvoltage during light loads
        large inductive loads such as of furnace or rectifiers, the   0  Overvoltage  may  saturate  transformer  cores  and
        fundamental content of the load current is high compared   generate harmonics
        to the individual harmonic contents. In all such cases, it   Failure of capacitor units and inductive loads connected
        is not necessary to provide a filter-circuit for each harmonic   in the system.
        unless the current is required to be as close to a sinusoidal
        waveform as possible, to cater to certain critical loads or   It should be ensured that under no condition of system
        instruments and devices or protective schemes operating   disturbance would  the  filter  circuit  become  capacitive
        in the system, where a small amount of harmonics may   when it approaches near resonance. To achieve this, the
        lead  to  malfunctioning  of  such  loads  and  devices.   filter circuits may be tuned to a little less than the defined
        Otherwise only the p.f. needs be improved to the desired   harmonic frequency. Doing so will make the Land hence
        level.  Also  to  eliminate  a  parallel  resonance  with  the   X, always higher than Xc, since
   784   785   786   787   788   789   790   791   792   793   794