Page 791 - Industrial Power Engineering and Applications Handbook
P. 791

Power capacitors: behaviour. switching and improvement of  power factor  23/747
           When such a reactance is used to suppress the system   Vph  = system voltage
         harmonics it will resonate at a frequency fh  such that
                                                              Vc = voltage across the capacitor banks = IC. Xc
                                                              VL = voltage across the series reactor = I,.  XI-
                                                        where
                                                             X,  = capacitive reactance
                                                              XL = inductive reactance. and
                                                              I,  = current through the capacitor circuit
                                                        then
                   -  '0 for a SO HZ  system
                   -                                         Vph = Vc  - Vl~ (phasor diagram, Figure 23.16(b))
                      0.06                                      = ICXC - ICX,
                  = 204 Hz. i.e. at the fourth harmonic.   and the rise in voltage across the capacitor banks. as a
           But when the third and/or second harmonics are also   ratio of the system voltage
         present in the system, at a certain fault level it is possible   k-   -   XC
                                                                 IC&
         that there  may  occur a parallel resonance between  the   Vp,   -   -  x, -x,       (73.8)
         capacitor circuit and the inductance of the system (source),   I,X,  -1,  XL
         resulting in very heavy third or second harmonic resonant   For a series reactor of 6%. for instance.
         currents. which may cause failure of the series reactor as
                                                            -
         well  as the capacitors. In such cases, a 6% reactor will   2- xc   = 1.0638
         not be relevant and a harmonic analysis will be mandatory   Vph   X,  - .06X,
         to provide more exacting filter circuits.     That is, the voltage across the capacitor banks will increase
           It  is  pertinent  to  note  that  since a  filter  circuit  will   by 6.38%. This voltage must be considered in the design
         provide a low impedance path to a few harmonic currents   of capacitor units.
         in the circuit (in the vicinity of the harmonic, to which it   Similarly, the third  harmonic may also be suppressed
         has  been  tuned) it  may  also  attract harmonic  currents   by  grounding  the  generator  or the  transformer  neutral
         from  neighbouring  circuits  which  would  otherwise   through a suitable impedance (LC circuit), as discussed
         circulate in those circuits. This may necessitate a slightly   in Section 23.5.2(c) and equation (23.6).
         oversized filter circuit. This aspect must be borne in mind
         when  designing  a filter circuit for a larger distribution   23.9.1  Compensating for the series reactor
         network having more than one load centre.
           It is, however, advisable to conduct a harmonic study   When a capacitor circuit is compensated through a series
         of the system to select a more appropriate size of reactor,   reactor, either to  suppress the  system  harmonics  or to
         particularly where the installation is expected to experience   limit  the  switching  inrush  currents  (Section  73.1 I)  or
         high harmonic disorders.                      both,  it  will  require  suitable  adjustment  in  its  voltage
           IJse of  a reactor will enhance the voltage across the   and capacitive ratings. The  series reactor  will  dampen
         capacitor banks and must be considered in the design of   the switching currents but consume an inductively reactive
         the  capacitor  units.  Refer  to  Figures  23.16(a) and  (b)   power and offset an equivalent amount of capacitive kVAr.
         illustrating this. If                         and require compensation. The following example will
                                                       elucidate this.
           R             I                              Example 23.1
                       1.                              To  determine the  basic parameters of  a  6% series  reactor

                                                       and its capacitive compensation, consider Example 23.6 with
                                                       3000 kVAr banks (1000 kVAr per phase) rated for 33.4 kV:
                                                         Then the  voltage  rating of  the capacitor  units should be
                        ri                               chosen for   33.4          from equation (23.8)
                                                              =  1.0638 x  Y
                                                                       >/ 3
                             i
              'WXL                                       say,  =   ~ 35.5  kV instead of
                                                                >b
                                                                33
                                                                     34
                                                                   or
                                                                     \3
                                                                73
                                            VC >  voh           - = kV               (see Figure 23.1  7)
                 (a) Power diagram
                                       (b) Phasor diagram   Since the  rating of  the series  reactor  is = 0.06  x  3000 =
                                                         180 kVAr.
         Figure 23.16 Voltage across the capacitor units rises with the   The capacitors' rating must be enhanced by the  rating of
         use of  series reactors                         the reactor to obtain the same level of effective kVAr.
   786   787   788   789   790   791   792   793   794   795   796