Page 794 - Industrial Power Engineering and Applications Handbook
P. 794

23/750 Industrial Power Engineering and Applications Handbook
        We  have ignored any leakage capacitance between line to   system  voltage,  as  shown  in  Tables  26.4  or  13.1  unless
        line or line to ground at 33 kV.               specified for still higher voltages by some users. Accordingly
                                                       equation  (23.8)  does  not  apply  in this  case.  Some  local
        Tackling the harmonics                         electricity distribution authorities, depending upon the likely
        To  eliminate all the harmonic contents from the supply it is   maximum voltage variation on their systems, may sometimes
        essential to provide shunt-filter circuits separately for each   ask for  still higher voltages.  But such distribution networks
        harmonic disorder. As  this  is a costly arrangement it is not   may not remain stable in the long run and must be improved
        followed  in  practice.  It  is  enough  to  drain  the  highest  (in   as far as possible with the use of reactive controls, as discussed
        magnitude) harmonic disorder. This will substantially improve   later.
        the  current  and  voltage  waveforms  and  make  the  circuit
        inductive for all higher harmonics, preventing a condition of   The above configuration or size of each unit is not mandatory
        resonance at any harmonic disorder during a line disturbance.   and can be altered, depending upon the economics of capacitor
        The  line  reactance and capacitance of  the capacitors  may   voltage and size of units available. Protection for all types of
        resonate at a frequency                        configurations  is easily available through various schemes
                                                       discussed in Section 26.1.
               1
         rh  =  -                              (23.6)
            2nm                                          From the above it can be inferred that for an accurate
          =  1.             1                          analysis of a system, particularly where the loads are of
                                                       varying  nature  or have  non-linear  characteristics  it  is
            2n   442.23 x   x 18.42 x lo6              necessary  to  conduct  a  harmonic  analysis. The  above
          = 180.5 HZ
                                                       corrective  measures  will  provide  a  reasonably  stable
        say,  at about the third or fourth  harmonics. But both these   network, operat-ing at high p.f. with the harmonics greatly
        harmonics are considered  negligible  in the  system  hence,   suppressed. The improved actual line loading, eliminating
        the filter circuit will be essential for  the fifth harmonic. The   the fifth harmonic component, which is compensated,
        series reactor required in the capacitor circuit is tuned, say,
        at about 225 Hz to be on the safe side, to account for variation                       I
        in  the  line  parameters  and  the  inductor  itself  to  keep  the   I;  = [4002 + 49 x 27.5'  + 121 x 10'  + 169 x 52]5
        circuit inductive under all conditions of line disturbances:
                                                          = 461.9A as against 525 A
         :.   27~ 225 x  L'  =   1
             x
                                                                              352
                       2rrx 225 x C                    and improved actual p.f.  = -
                    L'=           1                                          461.9
        or
                       (2n)'  x (225)'  x  18.42 x lo4                    = 0.76
                     = 27.2  mH                        and              44 = 40.5"
        or        XL'  = 2n x fx 27.2 x  10-3            A  phasor  diagram  (Figure  23.18(c))  illustrates  the
                     = 8.54 Q at fundamental frequency.   reduction in the actual loading and enhanced load transfer
                                                       capacity  of  the  network  which  can  be  achieved  with
        This  is  about 4.94%  of  Xc,  and  must be compensated  by   the  help  of  harmonic  suppressions. For  even  better
        providing additional capacitor units to maintain the required   utilization, the system may be tuned for higher harmonic
        level of  p.f. as discussed in Section 23.9.1.
                                                       disorders also.
         :.  Modified size of capacitor banks = 6300 x 1.0494
                                  = 661 1.2 kVAr
                                                       23.1 0  Excessive charging currents
        Let us choose a bank size of 6720 kVAr for easy selection of   (switching inrush or making
        each unit. To adopt a better protective scheme, let us select
        the configuration of a double star (Figure 25.5(b)).   c u r re n t  s)
         :.  Each bank for each arm of a double star
                                                       The circuit of an uncharged capacitor unit, when switched,
           - 6720                                      acts  like  a  short-circuit  due to  the  very  high  natural
           -~
              6                                        (transient) frequency&  of the switching circuit, causing
          = 1120 kVAr                                  the capacitor reactance X,,  to approach zero. The value
         Let  us  arrange  them  two  in  series  and  seven  in  parallel,   of the making current will depend upon the magnitude of
        based on recommendations made in Section 25.5.1 (iii) and   the applied voltage and the impedance of the circuit (motor
        as shown in Figure 23.18(b).                   and cables) or of the system that will form the switching
                                                       circuit. In other words, it will depend upon the fault level
         :.  Size of  each unit =  1120 = 80 kVAr      of the circuit and the rating of the capacitor units connected
                         2x7
                                                       in that circuit. This switching transient current, as illustrated
                          36*
        and voltage rating  =  -                       in Figure 23.19, as such being high, will be even higher
                         45x2                          if  the circuit already has some switched capacitor units
                       = 10.39 kV                      due to partial discharge of the already charged units into
                                                       the uncharged units, as discussed in Section 23.10.2. The
         *Note                                         behaviour of the capacitor switching circuit under various
        The  capacitor  units are generally designed for the  highest   switching conditions is described below.
   789   790   791   792   793   794   795   796   797   798   799