Page 932 - Industrial Power Engineering and Applications Handbook
P. 932

28/882  Industrial Power Engineering and Applications  Handbook



















                                 Figure 28.21  Graph to determine 0, of  a tubular bus section



         (through the busbars) and a higher voltage drop. In LT   of the other two phases, which would offset their proximity
         systems the spacings can be adjusted only marginally to   effects  (see  Figure  28.22).  The  conductor  of  phase  Y
         reduce  X,, as  a  lower  spacing  would  mean  a  higher   therefore would carry no distortion beyond the distortion
         electrodynamic force, F,  (equation  (28.4)) and greater   already caused by the skin effect (Rac/Rdc). The result of
         proximity  effects, requiring higher busbar  deratings. A   this would be that in a balanced three-phase system the
         compromise may therefore be drawn to economize on   three phases will assume different impedances and cause
         both.  In  HT systems,  however, which  require a  larger   an  unbalance  in  the  current  distribution. The  Y  phase
         spacing, no such compromise would generally be possible   having a smaller impedance, would share more current
         and they will normally have a high content of X,.  But in   compared  to the R  and B  phases  and cause a  smaller
         HT systems, voltage drop plays an insignificant role in   voltage drop. Such an effect may not be as pronounced
         view  of  a  lower  voltage  drop  as  a  percentage  of  the   in lower ratings and shorter lengths of current-carrying
         system voltage.                                conductors, as on  higher currents, depending upon the
                                                        spacing between the phases and the length of the system.
         28.8.2 Voltage unbalance as a consequence of the   Consider a feeding line from a transformer to a power
               proximity effect                         switchgear through a bus duct. The voltage available at
                                                        the distribution end of this feeding line may be unequal
         The proximity effect does not end here. It still has some   and tend  to cause a voltage unbalance. Depending upon
         far-reaching consequences in terms of  unequal  voltage   the rated current and length of the feeding line, it may
         drops in different phases at the same time. This is more   even cause a voltage unbalance beyond permissible limits
         so on large LT current-carrying, non-isolated bus systems   (Section  12.2) and render  the  system  unstable  and  in
         of  2000 A  and above, resulting  in  an unbalance  in the   some cases even unsuitable for an industrial application.
         supply voltage, as discussed below.              For  larger  current  systems,  2000 A  and  above  and
           A  three-phase  system  has  three  current-carrying   lengths  of  over  50  m,  a  correct  analysis  for  such  an
         conductors in close proximity. While the conductors of   effect must be made and corrective measures taken  to
         phases R and B will have an almost identical impedance,   equalize the voltage  and  current distribution in  all  the
         with the same skin and the proximity effects, the conductor   three phases. Where adequate precautions are not taken
         of phase Y is under the cumulative effect of electric fields   at  the  design  stage  through  phase  interleaving  or
                                                        transposition techniques, as discussed later, the problem
                                                        can still be solved by making up for the lost inductance
                   R           Y          B
                                                        in the Y phase by introducing an external inductance of
                                                        an appropriate value  in this  phase.  It  is  possible  to do
                                                        this  by  introducing  a  reactor  core  into  this  phase,  as
                                                        illustrated in Figure 28.23. This inductor will compensate
                                                        for the deficient inductance and equalize the impedances
                                                        in all three phases, thus making the system balanced and
                                                        stable. We illustrate briefly later a procedure to determine
                               t                        the  size of  a saturable  reactor core, when  required,  to
                                                        meet such a need.
               Influence of  electric fields of conductors Rand B is
              offset in a 3-4 system. The proximity effect in phase Y   Example 28.8
                        therefore gets nullified        Consider Example 28.6 to determine the content of proximity;
                                                        (i) For reactance X,  on account  of  the proximity  effect,  use
                  Figure 28.22  Influence of  proximity   Figure 28.16  and the graph of  Figure 28.24:
   927   928   929   930   931   932   933   934   935   936   937