Page 934 - Industrial Power Engineering and Applications Handbook
P. 934

28/884 Industrial Power Engineering and Applications Handbook
         this particular instance, one may reduce the content of        +
                                                                        R
         X,  by  reducing  S if  permissible,  or  consider  the  next
         higher cross-section of busbars. This size of bus section,
         in this particular instance, may be considered for a current
         rating up to 800 A.

         Example 28.9
         Consider Example 28.7 to determine the effect of proximity:
         (i) For the configuration of  Figure 28.17(a)
                      a  -  44.45 - 0.4375
                      b   101.60
                    S
               1.26  - = 1.26 x   184.45   ~  1.59
                   a+b        44.45  + 101.60
         then X,,  due to the proximity affect from the graph of Figure
         28.24,
           =  125Wm
         or   0.125C2/1000 m per phase and
         (ii) impedance,  z= d0.0186' + 0.125'
                                                       Figure 28.25  Distribution of  inductive reactance and
                      = 0.126 R/1000 m per phase and
                                                       impedance of  each phase in a three-phase system
         (iii)  voltage  drop, considering  a  length of  busbars as 40 m
         and current rating as 2000 A,
                         40                                  I,  = I,  = I, (say)
                        1000
           = 2000 x 0.1 26 x  ~
           = 10.08 V which is 2.43% for a 415 V  system
         The bus system is therefore suitable to carry 2000 A up to a
         length of  40  m.  Beyond this the voltage  drop may become
         higher  than  permissible  and the  bus  rating  may  call  for  a
         derating.

         Note
         The rating for this section considered here as 2000 A, is hypothetical
         and must be checked for the various design parameters as discussed
         already, in Sections 28.5 and 28.6, and analysed in Example 28.12.   (Basically these are all phasor quantities but for ease of
                                                       illustration absolute values are considered)
         Use of a saturable reactor (choke) to balance a
         large unbalanced power distribution system

         Determining  the size of reactor                            I, . Vph
         Consider a  three-phase bus  system as shown in  Figure   or Vph -I, X, = -
                                                                       I,
         28.27. If X, and X  are the inductive reactances of each
         phase on account of skin and proximity effects respectively,     I,  ' vph
         then the impedances of each of the three phases can be   I, . xp = Vph - -
                                                                            I,
         expressed as
         2,=R+X,+X,=Z                                   or

                                                         The values of I, and I, must be known to determine the
                                                        value of the reactor, Xp. Otherwise the reactance, X,,  as
         (since the Y phase will have no proximity effect)   determined earlier, to  account  for the proximity  effect
                                                        may be considered as the lost reactance in the Y phase
                                                        and for which the reactor may be designed for this phase.
           Therefore  inductive  reactance  equal  to  Xp must  be
         introduced  into  the  Y phase  to  equalize the  reactance   Designing a reactor
         distribution and make the system balanced (Figure 28.25).   The self-inductance
           If IR, Iy and IB are the currents in the three phases and
         Vph the phase voltage then
   929   930   931   932   933   934   935   936   937   938   939