Page 939 - Industrial Power Engineering and Applications Handbook
P. 939

Carrying power through metal-enclosed bus systems  281889
          For instance, a bus system with 4 x 152.4 x 6.35 mm
        conductors  may  be  arranged  into  two  groups  of  two   :.   ~  Ra,   from the graph in Figure 28.1 3 (a) by interpolation for
                                                         R dC
        conductors each, according to Figure 28.29(b). Then the   an EIE-M grade of  aluminium  = 1.1 3
        improved rating of this system as in Table 30.4 will be
                                                         Rdc = 0.056 Q/lOOO m per conductor
          = 2 x 2860
          = 5720 A                                         = 0.056/4 R/1000 m for 4 conductors
                                                                  0.056
        as against                                     :.  R,,  = 1.13 x -
                                                                   4
                                                           =  0.0158 R/1000 m
          4240 A  for  all  conductors  put  together  as  in  Figure
          28.331a) or                                  :.  Impedance  Z = 1/0.0158'  + 0.045'
          1.18 x  4240,  i.e. 5003 A  when  arranged  as  in
          arrangement 2 of  Figure 28.14.                         = 0.0477 R/1000 m

        Thus. in phase interleaving, there will be better utilization   Voltage drop
        of  conductor  capacity  by  5720/5003  or  >14%  over   Accordingly the revised voltage drop for 40 m of bus length
        arrangement 2 in Figure 28.14.                                 40
                                                        = 2000 x 0.0477 x   ~
                                                                      1000
        Example 28.1 1                                  = 3.82 V
        Consider Example 28.7 again, using four sections of  101.6 x
        6.35 mm AI conductors, now interleaved as shown in Figure   which is even less than  1% for a 415 V  bus system
        28.30. To determine the improved reactance and resistance
        of  this arrangement we can proceed as follows.   Electrodynamic forces
                                                      For a system fault level of  50 kA maximum forces on each
        Proximity effect:
                                                      group,
           a = 19.05 mm
           S = 94.05 mm
                                                      (i) For a conventional arrangement (Figure 28.17(a))

                            S  -  1.26 x 94.05
        and space factor,  1.26 x  -                  Kfor a space factor of  S-a - 184'45 - 44.45  i.e. 0.958
                                                                              44.45 + 101.6
                               -
                                                                        a + b
                          a+ b   19.05+ 101.6
                               = 0.98                 corresponding to  a or - 0.4375
                                                                            i.e.
                                                                       44.45
        X,  from graph of  Figure 28.24 = 90 pWm                    b   101.6
        and for two parallel circuits = 90/2          from the graph in Figure 28.7 by interpolation  K = 0.96
                                                            - 0.96 x 16 x 50000'
                            = 45 pR/m or 0.045 R/1000 m   .   rn  -           10-4
                                                       "          184.45
        as  against  125 @/m  with  the  conventional  arrangement
        calculated in Example 28.9.                        = 20 819 N/m
                                                      (ii) For the improvised interleaving arrangement in Figure 28.30:
        Skin effect
        Area of cross-section  per split phase = 2 x  101.6 x 6.35   K for  a  space  factor  of  94.05 - 19.05  i.e. 0.62 from  the
                                                                         19.05 + 101.6
                                   = 12.9 cm2         graph in Figure 28.7 corresponding to
        b   101.6
        - = - 5.33.
                 =
        a   19.05                                      a of 19.05 i.e. 0.1875  = 0.87
                                                           101.6
                                                       b
                                                       :.  F,  on each set of supports
          R       B
         6.35                                                             0.87 x  16 x [ 502000 )*
         + p-
                                                                         -                  x  lo4
                                                                                 94.05
                                                                        = 9250.4 Nlm
                                                       :.   F,,  on both supports = 2 x 9250.4
                                                                         = 18 500.8 Nim.
           6.35                                       This is less than the force developed with the conventional
        a = 19.05 mm                                  arrangement in Figure 28.17(a).
        b = 101.60 mm
        S = 94.05 mm                                  3 Phase transposition
        (Depending upon the current  rating, it would be advisable to keep it
        minimum 300 mm, by increasing the gap between the split phases.)   In this arrangement the three-phase conductors are evenly
               Figure 28.30  Illustrating Example 28.1 1   transposed in a length of busbars by  interchanging their
   934   935   936   937   938   939   940   941   942   943   944