Page 993 - Industrial Power Engineering and Applications Handbook
P. 993

31/938 Industrial  Power Engineering  and Applications  Handbook
        31.4  Enclosure heating                        Having  determined  RaC2", it  must  be  corrected  to  the
                                                       operating temperature by  using
        Heating of enclosures for bus systems in such large ratings   Rdce = Rdc2[)  1  + a20  (0 - 2011   (3 1.4)
        is detrimental to their design. In smaller ratings (say, up
        to 3200 A) it has been easier to do this by increasing the   where
        size of enclosure, choosing larger bus sections, changing   Rdce = d.c. resistance of the conductor at the operating
        their configuration or using a non-magnetic enclosure or   temperature
        by adopting more than one of these measures, as discussed   azo = temperature resistance coefficient of the metal at
         in Chapter 28. But this is not  the case in large ratings,   20°C per-"C  (Table 30.1)
         where heat  generated,  particularly  in  the  enclosure,  is   W,, W, and W, ( W,, when considering the outdoor part)
        enormous  due to  carrying almost the  same amount of   can thus be determined. The total heat, W,, so generated
         induced currents as the rating of  the  main  conductors.   can  be  naturally  dissipated  through  the  enclosure  by
         Therefore, dissipating the heat of the conductor and the   radiation and convection. If natural cooling is not adequate,
         enclosure is a major task in an IPB system. When designing   forced cooling can be adopted through forced air or water.
         such a system it is imperative to first check the adequacy   But precautions must be taken to ensure that the system
         of the enclosure to dissipate all the heat generated within   is protected from absorbing dirt, dust or moisture from
         permissible limits.                           the atmosphere.
          If the heat generated by induced currents (there are no
         magnetic losses) on load on per phase basis is   Note
         In the main conductor, due to  I,  = W, = IF2 . R, ,   For medium ratings as in a non-isolated bus system of up to 3200 A
         In the enclosure, due to  I,  = Wz If . R,    little significance is attached to such effects because of acomparatively
                                   =
         In  the outdoor portion of the enclosure, due to   weaker magnetic  field produced  by  the conductors of  each phase.
         solar radiation = Ws*                         andcancellation ofapart ofit by the fieldsoftheotherphases (Figure
         then the total  heat generated                28.22 and  Section 28.8). The enclosure currents are now  a much
                                                       lower percentage of the current of the main conductors and hence
         = W, + W, + Ws* in watts per unit  length   (31.2)   cause a low heating of the enclosure. The residual magnetic field in
           (*only for the outdoor parts)               suchcases is alsosmall andis  normallyignored.Yetcertaininstallations
                                                       may  require  magnetic shielding in  such ratings  also  where  these
         where                                         fields may influence the operation ofthe instruments that are installed
         I, = rated  current of  the main  conductors  in  Amperes   in the close vicinity.
             (r.m.s.)
         R, = a.c. resistance of the main conductors per unit length   31.4.1  Skin effect in a tubular conductor
             at the operating temperature, in R
         I,  = Induced current through the enclosure in Amperes   Tubular conductors provide the most efficient system for
             (r.m.s.). This will vary with the type of enclosure,   current carrying, particularly large currents. As discussed
                                                       above, the current  density  is  the maximum  at  the  skin
             the effectiveness of  its  electrical bonding and the
             impedance of the bonding links. If current limiting   (surface) of the conductor and falls rapidly towards the
             reactors are used in the enclosure circuit this current   core. Experiments have been conducted to establish the
                                                       normal pattern of current distribution in such conductors
             would be reduced substantially, as discussed above.   at different depths from the surface (Figure 3 1.11).
             Without  such current limiters, the current may be   At a certain depth, the current density reduces to 1/&=
             assumed to be up to 95% of I,.  Experiments have   0.368 of  the value  at the  surface. This depth is termed
             corroborated  this  assumption  in  continuous  bus   the depth of penetration, SP. Of the total  heat generated
             systems.
         Re = a.c. resistance of  the enclosure, per  unit  length at   in such conductors, almost 80% occurs within this depth
             the operating temperature in R.           (annulus). In other words, around 90% of the total current
                                                       heat generated  a 0.9'   2-  0.8 is concentrated in this area
           To determine R, and R, the same procedure may be   alone. This depth can be represented by
         adopted  as  discussed  in  Section  28.7.  For  a  tubular
         conductor,
                                                                                              (31.5)
                                               (3 1.3)   where
                                                        p= resistivity of the metal  in e.m.u.
                                                         = 1 O9  x (p in R cm) as in Table 30.1
         (in MKS or FPS units, depending upon the system adopted)   .f'= frequency of the system in Hz
         where                                          p  = effective permeability of the medium in which the
          p = resistivity of metal  at 20°C in  Rm or in pRcm   field  exists  (aluminium  in  the  present  case),  and
         d,  = mean diameter of the tube in m or cm        will  depend upon  the  electric field induced  in  the
          t = thickness of the tube in m or cm             enclosure
          I  = length of the conductor in m or cm        = I  for non-magnetic  materials
         From similar skin effect curves, as in Figure 28.13(b),   6, will thus vary with the material of the conductor and
         corresponding to tld the ratio Rac20/Rdc20 can be found.   the  enclosure  and  the  operating  temperature.  For
   988   989   990   991   992   993   994   995   996   997   998