Page 421 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 421

Be st Practice 7 .13          Lube, Seal and Control Oil System Best Practices
          A two way valve is a simple bypass around the cooler, while  Critical equipment trip instrumentation
       a three way valve is a true mixing valve. It should be noted that  A general critical equipment design philosophy is to avoid trip
       when sizing a two way valve, the pressure drop across the cooler
                                                            circuits as much as possible. That is, to only install trip switches
       must be known, to ensure that the valve coefficient is large  in those situations which are absolutely necessary. Typically,
       enough to pass the required flow. Many systems using two way
       valves are insufficiently sized. This can result in cooler oil con-  auxiliary systems incorporate only one trip function, such as the
                                                            low lubricating oil trip in lube systems and the low seal oil dif-
       stantly being supplied to the system, since the pressure drop  ferentials trip in seal systems. Sometimes a high temperature
       through the cooler is less than the minimum pressure drop  switch is also installed to trip, but this is not usually the case.
       through the control valve.
                                                            The setting of the trip switch is very important. It must be se-
                                                            lected such that the equipment will shut down when actuated in
       Instrumentation                                      order to prevent any long term damage. It must also be selected
                                                            to prevent spurious, unnecessary trips of the unit, since they are
       The instrumentation in any auxiliary system is extremely  extremely costly in loss of revenue. In addition, the quality of
       important in ensuring quick system response, accurate moni-  any trip switch is extremely important since this relatively low
       toring of system condition and rapid system shutdown in the  cost device could cost millions of dollars of lost product revenue
       event of upsets. In this section we will examine stand-by  per day if it malfunctions. Attention is drawn to correct selec-
       pump start-up operation, critical equipment shutdown and  tion of switch component materials to prevent corrosion or any
       monitoring functions of the instrumentation in the auxiliary  abnormality that would cause drifting of switch setting and
       system.                                              unnecessary unit shutdowns. Again the concept of a system is
                                                            extremely important to consider. It must be remembered that
                                                            the trip switch and the shutdown system for the critical
       Stand-by pump automatic start                        equipment must function accurately together in order to
       As previously mentioned, interrupting pumped flow to critical  terminate equipment operation immediately upon signal from
       equipment results in a rapid deterioration in system flow and  the initiating trip switch. ‘Best practice’ is to use smart
       pressure. Referring again to the concept of an equivalent vessel,  (self-diagnostic), triple redundant (two out of three voting)
       the absence of inlet flow to the system while exit flow is con-  transmitters for all pump start and trip services.
       tinuing will instantaneously produce a pressure drop. This con-
       cept is used in a pressure switch that signals the immediate start  Auxiliary system monitoring
       of the stand-by pump. Practice has shown that locating the  Refer to Figure 7.13.1 and observe the different monitoring and
       pressure switch takeoff as close as possible to the pump dis-  alarm functions normally used in an auxiliary system. In order to
       charge results in the quickest response time to start the stand-by  ensure reliable auxiliary system operation, the personnel must
       pump. Some systems incorporate dual pressure switches, one  continuously observe and record any changes in instrument
       close to the pump discharge and another up close to the critical  readings and promptly attend to alarms to ensure that the
       equipment. Both switches start the stand-by pump on signal.  system continues to operate as required. Changes in any of the
       The pressure setting of the switch is usually set just below the  system instruments indicates a change in the operating condition
       lowest discharge pressure that the pump will produce. In order  of the system, which must be followed through to make sure
       to ensure the rapid start of the auxiliary pump when required,  that components are operating as required. As an example,
       many systems incorporate an on-off-automatic switch on the  slowly deteriorating lube oil supply pressure could indicate
       auxiliary pump, or on the stand-by pump motor starter for  either a valve malfunction, reduction in speed of a main turbine
       testing the system. It is extremely important that the position of  pump driver, excessive pressure drop in the system oil filter or
       the switch always be in the automatic mode during critical  several other types of problem. It is extremely important to
       equipment operation. It is recommended that an alarm be  maintain a program of auxiliary system instrumentation cali-
       supplied and annunciated in the event that the auxiliary or  bration to ensure all instruments are reading properly. This will
       stand-by pump is not in the auto position during critical  aid greatly in determining system malfunctions and assist in the
       equipment operation.                                 site preventive maintenance program.





















           392
   416   417   418   419   420   421   422   423   424   425   426