Page 482 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 482

Lube, Seal and Control Oil System Best Practices  Best Practice 7 .34
              such a system, consideration should be given to a means of  this configuration, the control valve which senses its signal from
              changing the minimum flow and maximum flow orifice for  the level transmitter, will be sized to continuously supply the
              various operation points. Externally piped bypass orifices could  required flow to maintain a constant level in the overhead tack.
              be arranged such that a bypass line with a large orifice for  As an example, consider the following system changes from
              minimum suction pressure conditions could be installed and  start-up to normal operation.
              opened during this operation. It is important to note, however,  In this example a change from the start-up to operating
              that the entire supply system must be designed for this flow  condition will increase gas reference pressure on the liquid level
              condition and control valve must be sized properly to ensure  in the overhead tank and would tend to push the level down-
              proper flow at this condition. In addition, the low pressure  ward. Any movement of the level in the tank will result in an
              bypass line must be completely closed during normal high  increasing signal to the level control valve to open, thus in-
              pressure operation.                                  creasing the pressure (assuming a positive displacement pump)
                                                                   to the overhead tank and reestablishing the preset level.
              Example 3: Bushing gas side seal e bushing             In the above example, at 1,380 kPa (200 psi) reference
              atmospheric side seal with no flow through            pressure, the bypass valve would close considerably. To increase
              provision                                            the pressure supply of the seal oil from 34.5 to 1,410 kPa (5 to
                                                                   205 psi), the difference of bypass flow through the valve 27
              Figure 7.34.1 shows this type of seal system. In this type of  LPM (7 GPM) is equal to the increased flow through the at-
              system, the differential control valve becomes a level control  mospheric bushing at this higher differential pressure condition.
              valve sensing differential from the level in an overhead tank and  Utilizing the concept of equivalent orifices, it can be seen that
              is positioned upstream of the unit. Both bushings can be easily  the additional differential pressure across the atmospheric
              conceived as equivalent orifices. The gas side bushing flow will  bushing orifice is compensated for by reducing the effective
              remain constant regardless of differential. The atmospheric  orifice area of the bypass control valve. This is accomplished by
              bushing flow will vary according to seal chamber to atmospheric  sensing the level in the head tank and maintaining it at a constant
              pressure differential.                               value by opening the seal oil supply valve.
                Therefore, the atmospheric bushing must be designed to pass
                                                                     As in the case of the orificed through flow example above,
              a minimum flow at minimum pressure conditions that will  this configuration is susceptible to high atmospheric bushing
              remove frictional heat and thus prevent overheating and damage
                                                                   temperatures at low suction pressures and must be monitored
              to the seal. Since a gas side bushing seal is utilized, a minimum  during this condition. Repeated high temperatures during low
              differential across this orifice must be continuously maintained.  suction pressure conditions should give consideration to re-
                Utilizing the concept of head, the control of differential  sizing of atmospheric bushing clearances during the next avail-
              pressure across the inner seal is maintained by a column of  able turnaround. The original equipment manufacturer should
              liquid.                                              be consulted to ensure correct bushing sizing and supply system
                As an example, if the required gas side seal differential of oil  capability.
              to gas is 34.5 kPad (5 psid) by the liquid head equation:
                      Head ¼ 0:102 ð34:5Þ kPadÞ                    Example 4: Gas side bushing seal e atmospheric
                                             ¼ 4:1 meters
                                :85                                side bushing seal with through flow design
                              2:311   5 psid                       Refer to Figure 7.34.12. The only difference between this
                       Head ¼              ¼ 13:6ft:               system and the previous example is that a through-flow option is
                                   :85
                                                                   added to allow sufficient flow through the system during
                Therefore maintaining a liquid level of 4.1 m (13.6 ft) above
                                                                   changing pressure conditions. The bypass valve in the previous
              the seal while referencing process gas pressure will ensure  system is replaced in this system by a level control valve refer-
              a continuous 34.5 kPad (5 psid) gas side bushing differential. In
                                                                   enced from a head tank level transmitter, and is installed
                                                                   downstream of the seal chamber. This system functions in ex-
                                                                   actly the same way as the system in Example 1. The only dif-
                                                                   ference being that a level control valve in this example replaces
                                     Start-up                      the differential control valve in the previous example. Both
               Item                  condition   Normal operation
                                                                   valves have the same function, that is, to control the differential
               Compressor suction pressure 0 kPa (PSIG)  1,380 kPa (200  in the seal chamber between the seal oil supply and the refer-
                                                 PSIG)
               Overhead tank reference  0 kPa (PSIG)  1,380 kPa (200  enced gas pressure. A level control valve is utilized in this ex-
               pressure                          PSIG)             ample, however, since a bushing seal requires a significantly
                                                                   lower differential between the seal oil supply pressure and the
               Gas side seal bushing flow  0 LPM (GPM)  0 LPM (GPM)
               Atmospheric side seal  19 LPM (5 GPM) 46 LPM (12 GPM)  gas reference pressure.
               bushing flow                                           Consider the following example. Assume that a differential
               Seal pump flow         77 LPM (20  77 LPM (20 GPM)   control valve would be used as opposed to a level control valve for
                                     GPM)                          the system in Figure 7.34.12. For the start-up case, the differ-
               Bypass valve flow      58 LPM (15  31 LPM (8 GPM)    ential control valve would have to maintain a differential of 34.5
                                     GPM)
                                                                   kPa (5 psi) over the reference gas. When the reference gas
                                                                   pressure were 0, the oil upstream pressure to the valve would be
              Fig 7.34.11   Seal System Flow                       approximately 34.5 kPa (5 psi). For the operating case,

                                                                                                               453
   477   478   479   480   481   482   483   484   485   486   487