Page 309 - Industrial Power Engineering and Applications Handbook
P. 309

12/288  Industrial Power Engineering and Applications  Handbook
         Commencement                                                                  Current cut-off
         of short-circuit                                                             r level










                                    \\\ c 4 q
          5

           fs  = Pre-arcing time
           t, = Arcing time
            tt = Total cut-off time        Symmetrical
        isc(peak) value of a fault current   short-circuit
              Peak
             =
           is, = Peak cut-off current by fuse   current
              Figure 12.17  Cut-off feature of an HRC fuse



        12.4.2  Protection against fault conditions

        Protection against short-circuits
        (use of HRC fuses)                                 0.1 2
        It is always desirable to protect a power circuit against   o.2
        short-circuits separately. HRC fuses are the immediate   1   2   4   6  8  10   20  io 40  6080
        answer  to  such  a  requirement  for small  and  medium-     Symmetrical prospective --t
        sized LT motors. They have a delayed action characteristic   short-circuit current I,, (rms)(kA)
        under an overload and are instantaneous against a short-   Illustration:
        circuit  condition  and  thus  inherit  the  quality  of  dis-   A 320A fuse will cut-off an lSc of  30 kA (peak value
        crimination. They reduce the electromagnetic and thermal   up to 2.1 x 30 kA) at less than 15 kA (peak).
        stresses  and  enhance  the  withstand  capacity  of  the
        protected equipment for higher fault levels. Quite often,   Figure 12.18  Typical current cut-off characteristics for LT HRC fuses
        they are used on the receiving end side of a supply system   at prospective current up to 80 kA
        to enhance the short-circuit withstand capacity of all the
        equipment  connected  in  the  circuit  and  installed  after
        the HRC fuses. Figures  12.17-12.19  illustrate how  the   MCCB (moulded case circuit breaker) or MCB (miniature
        HRC fuses,  by  quickly  isolating  the  circuit  on a  fault   circuit  breaker)  and contactor]  and the  overload relay.
        well below the prospective fault level, reduce the electro-   These recommendations permit damage of components
        magnetic and thermal stresses on the connected equipment.   on fault to varying degrees as noted below:
        If the same fault had been cleared by an ordinary short-
        circuit relay  it could reach  its  momentary  peak  value,   Type  1: Under short-circuit conditions  the contactor
        which can rise to 2.2 times the r.m.s value of fault current   or the starter will cause no damage to the operator or
        in LT and 2.5 times in HT circuits (Table 13.1 1) as it had   the installation but may not remain suitable for further
        taken  more than  one-half  of  a cycle to clear the fault.   service without repairs or replacement of some of its
        For instance, a fuse of 320A, of characteristics shown in   parts. In other words, contact welding of the contactor
        Figure 12.18, will cut off a fault of 30 kA symmetrical,   is allowed and burnout of OCR is acceptable. In either
        with a crest (prospective) value of around 63 kA at only   case replacement of components may be necessary.
         15 kA, which is well below its prospective value.   Type 2: On the other hand, Type 2 degree of protection
                                                         limits  the  extent  of  damage  in  the  case  of  a  short-
        Selection and coordination of fuse rating        circuit. Now under short-circuit conditions, the contactor
                                                         or the starter will present no risk to the operator or the
        The  selection  should  be  such  as  to  provide  proper   installation and will remain suitable for further service.
        discrimination at the various levels of a multi-distribution   In  other  words,  no  damage  to  the  contactor  or  the
        network.  Our discussions generally take account of the   OCR is permitted. It may, however, be interpreted that
        recommendations in IEC 60947-4-1  regarding cooi-dina-   contact welding may be permissible to the extent that
        tion  between  the  short-circuit protection  and the main   the contactor can be put to service once again after a
        components such as switching devices [switch, breaker,   brief  period by  separating the contacts with the help
   304   305   306   307   308   309   310   311   312   313   314