Page 312 - Industrial Power Engineering and Applications Handbook
P. 312

Protection of electric motors  12/291
           have the required fault level, may be chosen with a lower setting   a built-in single-phasing protection or the tripping circuit
           of  the  OCR. This protection may,  however,  be  applied  in  an   is provided with a single-phasing preventor. If a separate
           MCB or an MCCB, when they possess a rupturing capacity less   protection for this is considered desirahle, one may use
           than  required.  Since  the  MCB  and  the  MCCB can  both  be
           current limiting the characteristics of the fuses and the breakers   a negative  phase sequence relay like the one shown in
           can  be  coordinated  such  that  faults that  are  in  excess  of  the   Figure  12.23(b) or similar  static or  PLC-based  relays.
           rupturing  capacity  of  the  breakers  alone  are handled  by  the   For larger motors, however, one should employ a relay
           fuses.                                      like a motor protection relay.  which covers in one unit
             In such cases it may often be possible to meet the requirement   all the protection as described in Section  12.5.
           by selecting a higher frame size of MCB or MCCB, which may
           possess a higher rupturing capacity also. If not, and to save on   Note  One  should  employ  only  current  \enring  relays ar  far  a\
           cost, one may provide HRC fuses for back-up protection.   possible for such applications as a negative sequence current has a
         7  -  To make a proper selection of HRC fuses it is essential that the   severe  effect  on  motor  windings  due  to  a  much  lower  negatiLe
           current-time  characteristic curves for the releases of the breaker   qequence  impedance  of  the  motor  (Section  1?.2(v)) than  ;I
           and the fuses are available from their manufacturers.   corresponding negative  sequence voltage.
                                                         Such a relay is connected on the supply side a\ shown in Figure
         Coordination of fuses with a switch  or a  contactor   12.23(a). The arrangement is such that unless the relay closes, the
         Since both these devices possess a certain level of making   motor  switching circuit  will  not  energize and  the  motor  will  not
         and breaking capacities, the same criteria will  apply as   start. The contact closes only  when  the  supply voltage  i\  normal
                                                       and the phase sequence positive. Even for undervoltage conditions.
         for the breaker noted earlier. Rating of fuses shall not be   the torque developed by the relay may not be adequate to close the
         more  than  the switch or contactor rating.   circuit. Such relays are, therefore, effective against
         Coordination of fuses  with a transformer     (i)   Negative  sequence  voltages  when  torque  developed  bq  it\
         Consider a distribution HV/LV transformer. If the fuses   coil is negative.
         are provided on both HV and LV sides, the fuses on the   (ii)  Voltages  far too low  to produce an  adequate  torque  to closc
                                                           the relay. This is possible during a start only. as during a run
         HV side must protect a fault within the transformer while   the  relay  contacts are already  established  and  the  coil  doer
         the fuses on the LV side must clear overcurrent and fault   not  detect  a fall in the voltage.
         conditions on the LV  side. Thus, for a fault on the LV   (iii)  Single phasing during a start. a% this will also produce a negative
         side, only the LV side fuses must operate and not the HV   torque  to close the relay.
         side, similar to the requirements discussed above.
           If  the  transformer  is  HV/HV,  the  same requirement   12.4.5 Protection against single phasing (SPP)
         must prevail, i.e. for a fault on the downstream (secondary
         side) only the downstream fuses must  operate and not   An ordinary thermal  relay senses only the line currents
         the fuses on the  upstream (primary side).    and is not suitable for detecting a single-phasing condition.
                                                       Referring to the curves of Figure 12.10, an ordinary relay
                                                       set at  110% of FLC will not trip in the event of a single
         ,Nore  It is. however, possible to eliminate the use of HRC fuses in   phasing when the motor is operating underloaded. say,
         LT hl~tems at least. with the availability of more advanced technology
         in an  MCCB or an MPCB (motor protection  circuit  breaker). See   at only 60% or less of the rated current, while in the lone
         Section  12.1 I  for D fuse-free system.      phase X, the current would be as high as 135% of FLC.
                                                         For  single-phasing  protection,  ‘single-phasing pre-
         12.4.3 Protection against stalling and        ventors’ are available. Although it is essential to protect
               locked rotor                            even a small motor against single phasing. there is little
                                                       point  in  employing these  preventors  unless  they  form
         Motors which  do not possess a  sufficient gap between   part of the basic starter (OCR with built-in  SPP feature)
         their hot withstand and starting curves generally call for   as an economic consideration.
         such a protection. Large LT motors and all HT motors   As discussed above, most of the leading manufacturers
         are recommended  to have a separate protection  against   of switchgear components produce thermal overcurrent
         such a condition. A locked rotor protection relay basically   relays with a built-in feature of single-phasing prevention.
         is an overcurrent relay, having an adjustable definite time   The use of a separate single-phasing preventor device is
         delay to trip the motor when  it exceeds its permissible   thus not  necessary  up to medium-sized  motors,  where
         starting time,  but  before  the  safe stall  withstand  time.   this  feature is available in  the relays. For large-motors
         This  feature  is  available  in  a  motor  protection  relay   and for critical installations, a  separate unit  for single-
         discussed later. Where, however, such a relay (MPR) is   phase  protection  may  be  required  for  prompt  single-
         not provided, a high-set IDMT overcurrent relay can be   phasing alarm and/or trip. Interestingly, where star delta
         chosen  to match the upper range of  the motor thermal   switching  is  employed, the overload  relays, which  are
         withstand curve (Figure  12.16).              now  connected  in  phases  of  the  motor  windings,
                                                       automatically sense an abnormal condition in any 01- all
         12.4.4 Protection against voltage unbalance or   the phases, and provide a single-phasing protection. See
               negative phase sequence                 the power circuit diagram in Figure  13.56 for more clarity.
                                                         A separate single-phasing protection device is available
         Such  a  condition  also  generates  negative  sequence   in two versions:
         components. For  small and medium-sized  motors, say,
         up to 100 h.p., no separate protection for such a condition   1  Voltage  sensing, and
         is normally essential, when the overcurrent relay possesses   2  Current sensing
   307   308   309   310   311   312   313   314   315   316   317