Page 310 - Industrial Power Engineering and Applications Handbook
P. 310

Protection of electric motors  12/289
































                                           Prospective current in amps (r.m.s) -

                          10   20    50   100   200   500 1000  2000   5000  10 000 20 000  50 000


                                      Figure 12.19  HRC fuse characteristics




        of a tool such as a screw-driver but without calling for
        replacement  of any part.
        Type 2 coordination is more prevalent and commonly
       used for all industrial applications. Below, we concentrate
       on coordination Type 2, permitting the least damage and
       longer service life. This coordination can safely withstand
       normal fluctuations in system parameters and operating
       conditions during normal working. It is always advisable
       to verify the authenticity of the coordination in a laboratory.
       For  procedure,  to  establish  the  type  of  co-ordination,
       refer  to  IEC  60298. To  achieve  the  required  precise
       coordination  we discuss a few typical cases below.
       Discrimination  between fuse to fuse
       Refer to the normal distribution network of Figure 12.20.
       Selection of the fuse ratings must be made on the following
       basis:

       (a)  Only fuses nearest  to the fault should operate.  For   F, f
          instance, for a fault at location C, the only fuses at
          location  C  should operate and not those at B or A.
       (b) To ensure the above, the total arc energy, Z2  . tt, of the
          lower fuses at C should be less than the pre-arcing   Figure 12.20  Coordination of fuse ratings and their
          energy, I2  t, of the upper fuses at locations B or A.   characteristics
   305   306   307   308   309   310   311   312   313   314   315