Page 313 - Industrial Power Engineering and Applications Handbook
P. 313

la292 Industrial Power Engineering and Applications  Handbook

             R  Y  B
             T T T













                      sequence voltage


                    ---
                                                         Static negative sequence relay (Courtesy: English Electric)



                                I
                                      N





       Figure 12.23(a)  Schematic for a negative phase sequence
       (NPS) relay



       Voltage-sensing preventors have limitations and are not
       reliable  since  they  offer  protection  up  to  the  sensing
       terminals only. Protection  beyond these terminals up to
       the  motor  terminals  is  not  possible.  In  the  event  of  a
       phase  failure  beyond  this  point,  the  voltage-sensing   PLC or micro-processor-based negative sequence relay
       equipment  will  not  detect  this.  (See  the  schematic of   (Courtesy: Alstom)
       Figure  12.24.) Current-sensing preventors are therefore
       recommended  for  more  reliable  detection  of  a  fault      Figure 12.23(b)
       anywhere within the system up to the motor terminals.
       Moreover, voltage-sensing preventors may act erratically,   control circuit to trip the starter unit. To avoid nuisance
       when the motor is generating high back e.m.f. on single   tripping, due to surges and momentary line disturbances,
       phasing,  and also when the power  factor improvement   a time delay  of 4 to 7 seconds is normally  introduced
       capacitors are connected across the motor terminals. In   into the tripping scheme.
       this  case high  back  e.m.f.  can  be produced  across the
       voltage-sensing  relays,  which  can  make  its  operation   12.4.6 Protection against voltage surges
       uncertain.                                           (for systems 2.4 kV and above)
         The current-sensing  solid-state type relays consist of
       a filter  circuit to  sense  the  negative  sequence  current.   Voltage surges may be of two types, external or internal
       The output of this filter is proportional  to the negative   (Section  17.5). A motor will require protection  against
       sequence component of the current. The output is fed to   both for absolute safety. For external  surges, lightning
       a sensor, which  detects the level of  negative sequence   arresters are provided as standard practice at the receiving
       component of  current and trips the starter circuit when   end as illustrated in Figure 12.27, to protect the electrical
       this  level  exceeds the  set  limit.  (See  Figure  12.25.)   installation as a whole. This lightning arrester will limit
       Normally  such preventors  are designed up to 30 A for   line surges due to external causes, within safe limits as
       motors up to 20 h.p. For larger motors, the output current   in Table  13.2 for  series I or Tables  14.1 and  14.2 for
       can  be  sensed  through  CTs of  5 A  secondary  (Figure   series I1 voltage  systems.  In  all likelihood  it  will  also
       12.26).  5A  secondary  is  chosen  to  make  detection   protect the main insulation of the rotating machines. The
       easy.                                          insulation level of a motor is much less than other electrical
         At  a preset  value,  the relay  operates and  opens the   equipment such as transformers and switchgears connected
   308   309   310   311   312   313   314   315   316   317   318