Page 403 - Industrial Power Engineering and Applications Handbook
P. 403

Switchgear and controlgear assemblies  13/377
           6  For  a  positive  ground  connection  and  to  provide   and  eliminate  arcing  between  them.  Otherwise  it
             total safety for the operator, a spring-loaded scraping-   may develop hot spots and result in corrosion of the
             type grounding assembly may be provided on each   contacts in the normal operation. It may also lead to
             trolley so that the moving part can slide on the fixed   an eventual failure of the joint/contact.
             grounding  strip  fitted  in  the  assembly,  and  make
             before  and  break  after  the  power  contacts  have
             engaged  or  disengaged  respectively.  Figures  13.2   N(Jtc
             and  13.35  illustrate  such  an  arrangement.  The   The main incoming male contacts are generally  made of copper or
             grounding contact may be of brass and silver plated   brass and are either bolted or clamped on the vertical bus. Since the
                                                        bus is generally of aluminium. the contacts may  form a bimetallic
             (a good practice).  It  may  be  fitted  on  the  tray  of   joint with the bu\bars and cause corrosion and pitting of the metal.
             each  module  and  permanently  connected  to  the   This may result in a failure of the joint in due courTe. To minimize
             ground bus running vertically  through each vertical   metal oxidation and bimetallic corrosion, the contacts must be silver
             panel  and connected to the main horizontal ground   plated.
             bus.                                         If  the  main  incoming  male  contacts are  made  of  aluminium
               A  positive  grounding  arrangement  will  mean   alloy, which  ic normally  a composition of  aluminium-magnesium
             automatic grounding of the trolley  as soon as it is   and  silicon, they  must be provided  with a coat of bronre. copper
             mounted on the tray for racking-in and then remaining   and tin to give it an adequate mechanical hardness and reriqtance to
                                                        corrosion.  For  more details refer  to Section 29.2.5.
             in permanent contact with the ground contact when
             the trolley  is fully racked into its service position.
           7  In a draw-out MCC, it is recommended that shrouds   10  Each trolley is recommended to possess three distinct
             are provided at the main  incoming power contacts,   positions of  movement, as shown in Figure  13.36.
             from  where  the  vertical  bus is  tapped, to feed the   i.e.  ‘service’, ‘test’ and ‘isolation’:
             draw-out module. Manufacturers may adopt different   Service: this is the position of the trolley when it is
             practices  to  achieve  this.  The  most  common  is  a   fully inserted into its housing (module) and the power
             DMC/SMC  (Bakelite,  which  was  more  common   and control contacts are fully made.
             earlier, is now being discarded, being hygroscopic   Test: This  is  the  position  of  the  trolley  when  the
             and inflammable) gravity-operated drop-down shutter,   power contacts are isolated but the control circuit is
             which  lifts automatically while the trolley  is being   still  connected,  because  it  is  lapped directly from
             racked  in  and  slides  down  as the  trolley  is  being   the  auxiliary  bus.  This  condition  is  essential  to
             racked out. Refer to Figure 13.35, showing a feeder   facilitate testing of control circuits with functional
             with the shroud lifted. Figure 13.2 also illustrates a   interlocks, without energizing the connected load.
             few feeders with  shrouds fitted. One of the feeders   Isolation: This is the position of  the  trolley  when
             is shown with  a lifted  shroud.              the power and the control circuits are both isolated.
           8  Indicating instruments, lamps, pushbuttons, selector   Depending  upon  the  site requirements,  sometimes
             switches  and reset knobs etc.  are mounted  on the   the control circuit may be required to be still energized
             trolley on a hinged auxiliary door, as shown in Figures   for some test requirements.
             13.2 and  13.12.                           11  The feeder door should not close unless the trolley
              The main outer door on the frame may have either   is racked-in, up to the test position  at least.
             an opening to seat the auxiliary door of the trolley   12  The trolley should not permit its withdrawal when
             on it or telescopic knock-outs for all such door mounts   its switch is in the ON position.
             to  provide  a  peep-through  type  of  aperture.  On it   13  While racking-out the trolley, it should not be possible
             are mounted the light and pushbutton tops. Figures   to completely withdraw it unless it has reached the
             13.2 and  13.12 illustrate this  type of arrangement.   ‘isolation’ position.  In  the isolation position  there
             The latter alternative provides a better arrangement,   must be a ‘holding-on’ latch arrangement, to prevent
             for it ensures a greater degree of protection. It has   an abrupt fall of the trolley from its module. Figure
             the most  significant advantage  when the trolley is   13.36 illustrates this feature.
             removed  from  its  module  and the  outer  door  can   14  Interchangeability of a module with another module
             still be securely shut on the module to provide total   of the same type and size is the basic requirement of
             protection for the empty module from dust, vermin   such panels.
             and rodents  as well  as inadvertent human  contact   15  Provision of an extra interlocking facility (peg and
             with the live incoming terminals. In the other design,   hole  system)  may  also  be  essential  to  prevent
             the  outer  door  has  a  large  knock-out  to  seat  the   interchangeability between two similar trolleys when
             auxiliary door.  which  may  remain  open when  the   the  circuits  or  the functions  of  the two otherwise
             trolley is removed for repairs or replacement,  and   identical trolleys  are different, and it is undesirable
             expose the interiors.                         to interchange these trolleys.
           9  Low  contact  resistance  is  desirable  at  all current-   16  Withdrawal  of  a  draw-out  circuit  breakcr  or  a
             carrying contacts, such as the busbar joints, between   withdrawable switch or contactor will not be possible
             busbars  and  the  incoming  fixed  power  contacts,   unless they  are in an OFF position.
             between incoming fixed power contacts and incoming   17  Operation  of  withdrawable  equipment,  such  as  a
             moving power contacts on the trolley and between   breaker or components on a withdrawable chassis,
             the outgoing moving and fixed power contacts etc.   will not be possible unless it is in service, test. isolated
             This is to ensure proper surface-to-surface contact   or totally removed positions.
   398   399   400   401   402   403   404   405   406   407   408