Page 457 - Industrial Power Engineering and Applications Handbook
P. 457

Testing of metal-enclosed switchgear assemblies  14/431


                               Momentary peak or making current (6), Table 13.11
                               Asymmetrical peak current envelopes
                               Asymmetrical average fault current, lav










                                                                                               I
                                                                                              fiJr







                       Sub-transient state
                                      Duration of  fault
        Note  The curves C, C2 and C3 C4 are considered  symmetrical after the first few cycles say 4 to 5. For better clarity, these 4 cycles are
        redrawn in  an enlarged form in  Figure  14.6
       Figure 14.5  Determining the average r.m.s. value of the short-time current /=from the oscillogram obtained during a short-circuit test


       will represent the asymmetrical r.m.s. short-circuit current   sustain the asymmetry for the period up to its opening. It
       (or the asymmetrical breaking current of an interrupting   may  also be referred  to as the interrupting duty of  the
       device) at the instants O1.                    device.
       Notes                                          Making current
       1  The d.c. component, Idc, at any instant should be a minimum of   This  is the  same  as  the  momentary  peak  value  of  the
         50% that of the corresponding peak value of the a.c. component   fault  current  INI and  defines  the  capability  of  the
         of  the symmetrical fault current I,,,.  lac,, ..., laclo, it. at any   interrupting device to make on fault.
         instant, during the period of the short-circuit condition, l,, should
         be 2 0.5 . 42 . Iac.  Otherwise the asymmetry may be ignored,
         being insignificant.                         Short-circuit generator (Figure 14.3)
       2   The peak  value of  the asymmetrical fault current determined
         for the first maximum peak may be considered as the momentary   Since this equipment is short-circuited  repeatedly  it is
         peak value of the fault current 1~.          specially braced to withstand repeated voltage transients
       3   The oscillogram  also reveals the  following vital  information   and  is  mounted  on  a  resilient  base  to  minimize  the
         for an  interrupting device,  if  used  in  the circuit, to make or   mechanical shocks transmitted to the base. If the generator
         break on fault;
                                                      is motor driven it is disconnected just before creating the
                                                      short-circuit condition, otherwise the generator may have
       Symmetrical breaking current                   to feed the motor and be subject to stress. The stator has
       This is the steady-state symmetrical fault current, which   low reactance to give maximum short-circuit output and
       the faulty circuit may almost achieve in about three or   has two windings per phase as illustrated in Figure 14.7.
       four cycles  from  commencement of  the  short-circuit   These  are  arranged  so  that  they  can  be  connected  in
       condition  at  point  DI (Figure  14.5) and  which  the   series or parallel,  in  star or delta etc.,  to provide four
       interrupting device should be able to break successfully.   basic three-phase  voltage systems as  follows:

       R.M.S.  asymmetrical  breaking current           Stator connections      Nominal voltage
       This is the r.m.s. value of the asymmetrical fault current
       Io, I,, ..., Zlo  that the faulty circuit may generate, i.e.   1  Parallel delta   6.35  kV
                                                                                ax6.35= 11.OkV
       I,,  = d    m                                  2  Parallel star          12.7 kV
                                                      3  Series delta
       It will determine the ability of the interrupting device to   4  Series star   x 12.7 = 22 kV
   452   453   454   455   456   457   458   459   460   461   462