Page 458 - Industrial Power Engineering and Applications Handbook
P. 458

14/432  Industrial Power Engineering and Applications  Handbook
                                                       Testing of the main circuits (with short-circuit
                                                      protective devices)
                                                         For a switching device (which has not been previously
                                                         tested for a short-circuit test).  This should be closed
                                                         and held in the normal service position. The test voltage
                                                         (that would generate the required level of fault current)
                                                         may  be  applied  on one set  of  terminals,  the  other
                                                         terminals being  shorted. The test may be continued
                                                         until the short-circuit device operates to clear the fault,
                                                         but in no case for less than 10 cycles. In LT assemblies
         4                                               the point where the short-circuit is created should be
                                                         2 f 0.4 m from the nearest point of supply.
                                                         For a switching device having no protection (e.g.
                                                         an Isolator).  The required test current may be applied
                                                         for the necessary  duration  (1  or 3 seconds) and the
                                                         dynamic and thermal strengths should be verified.
                                                         For the main busbars
                                                         -   In LT assemblies, when the test is conducted on
                                                            busbars, the length of busbars should be minimum
                                                            2 m.  If  it is less than this,  short-circuit may  be
                                                            created at the ends of the busbars.
                                                         -   If the busbars consist of more than one section in
                                                            cross-section, or different distances between the
                                                            supports or the busbars, the test may be conducted
                                J                        Test results
                                                            separately on each section.
                                                         -   A  successful test  should reveal no undue defor-
         Figure 14.6  Illustration of asymmetry during a short-circuit   mation. Slight deformation of busbars is acceptable
                                                            provided  that  the  clearance and  the  creepage
                                                            distances, as given  in Tables 28.4  and 28.5,  are
                                                            maintained. The insulation of the conductors and
                                                            the  mounting  supports should  show  no  sign  of
                                                            deterioration. The degree of  protection  will  not
                                                            be impaired.
                                                         -   For withdrawable parts, such as a draw-out breaker
                                                            or a  draw-out chassis, proper  movement of  the
                                                            movable parts and making of the contacts should
                                                            be ensured. To verify this requirement, the chassis
                                                            may be moved in and out for at least 50 times.
                                                         -   Clearance  and  creepage  distances  must  be
                                                            maintained in the service, test and isolated posi-
                                                            tions.
                                     I     1     I     14.3.7 Verification of momentary peak or

              (i) Parallel delta       (ii) Parallel star    dynamic current
                                                       This test is carried out to verify the mechanical fitness of
                                                       the buses, their interconnections, other current-carrying
                                                       parts  and  the  mounting  structure  to  withstand  the
                                                       electrodynamic  forces  developed  during  a  fault.  It  is
                                                       measured by the first major peak (IM) of the oscillogram
                                                       as discussed above and is obtained during the course of
                                                       the  short-time rating  test  (Section  14.3.6).  The  value
                                                       obtained  will  not be less than those  specified in Table
                                                       13.1 1. For more details see Section.  13.4.1(8). The test
                                                       procedure and the test current are generally the same as
                                                       for the short-time rating test, except that when the test is
                                                       being conducted exclusively to determine the momentary
                                                       peak current, the duration must not be less than 0.3 second,
            (iii) Series delta        (iv) Series star   Le. 15 cycles for a 50 Hz system as in IEC 60694. Refemng
          Figure 14.7  Arrangements of windings  in a test generator   to the oscillogram of Figure 14.5, the momentary  pear<
   453   454   455   456   457   458   459   460   461   462   463