Page 459 - Industrial Power Engineering and Applications Handbook
P. 459

Testing of metal-enclosed switchgear assemblies 141433
      value of  the fault current of  the first major  loop, after   2  Test current IR = 39.6 kA
      commencement  of  the fault condition  at instant D1, is   /y = 47.2 kA
      indicated  as ZM. Referring  to  the  original  oscillogram,   /B  = 41.2 kA
      (Figure 14.4), it occurs in phase  Z             Highest of the above exists in phase Y at 47.2 kA
                                                       :.  equivalent current rating of  the equipment under test
      Example 14.1                                     for
      For more clarity we have reproduced in Figure 14.3 an actual   1 second = 47.2.  J116
      test circuit and in Figure 14.4, the oscillograms of  the test
      results of  a short-circuit test successfully carried out on an
      LT power distribution panel (Figure 14.8) for a system fault
      level  of 50 kAfor 1 second, at CPRl (Central Power Research
      Institute). From a study of these oscillograms (Figure 14.4),   = 47.2 x  1.077
      we can infer the following test results:
                                                        = 50.836 kA
      1  No. of completed test cycles = 58           3  The maximum peak current also appears in phase Yand
                                                       measures at 110.6 kA at the first loop of the current wave.
                                     58
                                       =
         :.  duration of test for a 50 Hz system = - 1.1 6 second   This loop is 11 0.6/50, i.e. 2.21 times the test current and
                                     50                satisfies the requirement of Table 13.11.
                                                     Analysis of the test results
                                                     As discussed  above we establish  two basic parameters
                                                     from a short-time withstand test, i.e.

                                                     1  Thermal  capability  of the equipment under test, Le.
                                                       I,,  and its duration
                                                     2  Mechanical  compatibility  through  the peak  making
                                                       current, ZM, as in Table 13.1 1.

                                                       Before creating a fault condition, to obtain the required
                                                     Zsc  the impedance of the test circuit is adjusted  so that
                                                     the required fault current is obtained in all the phases on
                                                     creating a short-circuit. To provide the required thermal
                                                     effect  (Z:  . t), the duration of  test,  t, is then adjusted
                                                     accor-dingly. The relevant standards therefore  stipulate
                                                     that the test current may be higher or lower than required
                                                     and can be compensated by adjusting its duration, t.
                                                       However,  due to  the  minor  variations  in  the  phase
                                                     impedances,  all  the  phases  may  not  be  subjected  to
                                                     identical  severity  of  faults. For  instance,  in the  above
                                                     test each phase has recorded a different fault current. To
                                                     evaluate the fault level from these test data, the general
                                                     practice has been to consider the phase that has recorded
                                                     the highest fault current as the base, which may occur in
                                                     any of the phases.  In the above test, it has occurred in
                                                     phaseY. For this fault current, the test duration is adjusted
                                                     to achieve the required severity of fault in terms of thermal
                                                     effect (502 x 1 in the above case).
                                                       Some userslconsultants,  however, are of  the opinion
                                                     that by this method the other phases are not subjected to
                                                     the same severity. Accordingly, they prefer to consider
                                                     the phase that is subjected to the least fault current as the
                                                     base. Accordingly, the test duration  should be adjusted
                                                     for this phase. In the above case, the minimum severity
                                                     has occurred in phase R, with only 39.6 kA. According
                                                     to this philosophy the test duration should be enhanced to

                                                     502     or 1.59 s
                                                      (39.6)2
                                                     as against  1.16 s in the above test.
                                                       Even then it is essential, that the peak making current,
      Figure 14.8  A  motor control centre (MCC)  after short-circuit   ZM, of the required magnitude is achieved during the test.
      test at CPRl                                   This  is  one  parameter  that  cannot  be  established  by
   454   455   456   457   458   459   460   461   462   463   464