Page 636 - Industrial Power Engineering and Applications Handbook
P. 636

Surge arresters: application and selection  18601
          Moreover, as the surge travels through the primary to   and that  are subject to the power frequency withstand
        the  secondary  of  the  transformer.  a  part  will  become   test.
        dampened due to  partial  discharge  of  the  surge to the   During a high-frequency  (FOW) surge.  the inductive
        ground through the capacitive coupling  and also partly   impedance of the windings becomes very high and offers
        through  the  inductive  coupling  of  the  transformer. As   an  open  circuit  to  the  arriving  surge,  and  there  is  no
        the surge travels forward it will encounter the system’s   inductive transference of voltage surges to the secondary.
        (interconnecting  cables  and  the  terminal  equipment)   But at lower frequencies, such as during overvoltages,
        capacitive and inductive couplings, and will continue to   long-duration switching surges (250/2500 ps), and even
        attenuate in steepness as a result of electrostatic discharges,   during  lightning  surges,  the  windings  acquire  enough
        and in amplitude due to inductance of the circuit. In fact,   inductive continuity to transfer a part  of these voltages
        additional surge capacitors (C’) can be provided across   to the secondary, depending upon  the J; of the arriving
        the secondary windings as illustrated in Figure 18.13, to   surge, in  the ratio of  their transformation  (V2/VI). It is
        further dampen the  arriving transferred  surges. In fact,   generally noticed that  such transferences hardly  exceed
        this practice is sometimes adopted.            the power frequency withstand level of the windings and
          For adequate insulation coordination it is mandatory   are thus less critical. Nevertheless they must be counter-
        to  first  check  such  transferences  with  the  BIL  of  the   checked  while  designing  the  surge  protection  scheme
        transformer’s tertiary and secondary windings. The tertiary   for the whole system. If it is higher, then
         is a crucial winding and any damage to this will mean a
        major breakdown of the transformer. For the purpose of   The arrester on the primary side may be selected  with
        protection and to be more conservative, these calculations   a lower residual voltage (VreJ.  or
        may  be  carried  out  with  the  LV  side  open-circuited.   The tertiary  and secondary windings may  be selected
        Similarly, on  the  primary  side,  the  most  severe  surge   for a yet higher BIL if possible. or
        such as an  FOW may be  considered. If  the transferred   e  An  additional  arrester on  the tertiary  and  secondary
        surge  exceeds  the  BIL of  the  tertiary  and  secondary   sides must be provided.
        windings, one or more of the following protective mea-
        sures may  be considered:
                                                         IEC  6007 1-2  suggests  the  following  formula  to
                                                       determine such  voltages:
          When  the primary  is provided with an arrester, select
          one with a lower V,,,, to shield the secondary side also.   V,
          Consider tertiary and secondary windings with a higher   V,, = p.q.r  -            (I 8.8)
          BIL. if  possible.
          But  the tertiary  must  be  specifically protected by the   where
          use of an additional surge arrester between each of its   p  = factor for power frequency voltage already existing,
          phases and the ground. It is possible that this arrester   when  an overvoltage or a long-duration switching
          may discharge rather too quickly compared to the main   surge occur as noted  above.
          arrester on the primary in view of larger transferences,   q = response factor of the  lower voltage circuit to the
          compared to a very  low  voltage rating of the tertiary.   arriving long-duration surges (for power frequency
          If this occurs, the arrester at the tertiary may fail. The   transferences 9 = 1  and for FOWs 4  = 0).
          rating  of  the  tertiary  arrester,  therefore,  must  be   (i)  For secondary open-circuited.
          meticulously coordinated with the V,,, of the primary   lightning surges q 5 1.3, and
          arrester. The V,,, of the tertiary  arrester may have to   switching surges q 5 1.8.
          be  chosen  high  and  $0 the tertiary must be designed   (ii)  For loaded secondary q < I  .O.
          for a higher BIL.
          Use surge capacitances across the secondary windings.   It is seen that  normally it  may  not  exceed  1 .O  due to
          Generally, an arrester on the primary should be adequate   many factors, such as the  secondary may not be open-
          to protect the  secondary windings. When  it  is not, a   circuited, and the circuit parameters. L  and C. that the
          separate arrester may be provided between each phase   arriving surge may have to encounter with both having a
          and ground of the secondary windings.        dampening effect:
          The terminal equipment connected on the  secondary
          side of the transformer is thus automatically protected   r  = a  factor  that  will  depend  upon  the  transformer
          as it is subject to much less and attenuated severity of   connections, as indicated in Figure  18.14
          the transferred surges than the secondary windings of   V,  = a prospective long-duration  switching surge voltage
          the  transformer.  Nevertheless,  the  BIL  of  the   that may appear on the primary side. If an arrester
          interconnec-ting  cables  and  the  terminal  equipment   is  provided  on  the  primary  side.  this  may  be
          must  be  properly  coordinated  with  the  BIL  of  the   substituted with the switching surge residual voltage
          transformer  secondary,  particularly  for  larger   of the arrester, V,,,
          installations. say, 50 MVA and above, to be absolutely   n  = transformation ratio of the transformer ( VI/V2)
          ufe. Example  18.2 will  explain the procedure.
                                                       Example 18.2
        Electromagnetic transference                   Consider segment Xof Figure 18.25 for the purpose of surge
                                                       protection. The detailed working is provided in a tabular form,
        This is for systems having secondary voltages up to 245 kV   for  more clarity, as under:
   631   632   633   634   635   636   637   638   639   640   641