Page 644 - Industrial Power Engineering and Applications Handbook
P. 644

Surge arresters: application and selection  18/609






















                          ”.,  ,
                            0.1

                               Figure 18.16(b)  Typical TOV capability of  a station class arrester


         From the reproduced protective characteristics of this arrester,   Zz = surge impedance of the equipment to be protected
         as in Table 18.11, the nearest next higher rating available is   Z,  = surge impedance of the arrester at  C’[
         336 kV for a 420 kV system voltage. This is the basic rating
         of  the arrester which must be further  checked for
                                                       Then applying Thevenin’sY’ theorem, the equivalent circuit
                                                       can  be  represented  as  shown  in  Figure  18.18(b). On
           Whether its protective level can protect the BIL of the system
           and/or the equipment it  is protecting, and   application  of  a  voltage  surge.  the  arrester  will  start
           its  energy  capability  to  clear  safely  the  long-duration
           prospective voltage surges.
                                                       2’Thevenin’s theorem: This is one of  the many  theorem5 deduced
                                                       mathematically  to  solve  intricate  circuit. This  theorem  has
         Note
         Increasing the TOV  level, i.e. choosing a higher  protective   established  that  it  is  possible  to  replace  any  network  with  linear
         level (V,,,)  of the arrester, may increase the life of the arrester   parameters  and  comtant phasor  voltage  source\.  a5  vieu cd from
         but  will  reduce  the  margin  of  protection for  the  protected   terminals,  a  and  h.  Figure  18.19(a). by  a  \ingle  phasor  voltage
                                                       source E  with  a single series impedance Z. Figure  18.19rb). The
         equipment. Selection therefore should be  done judiciously   voltage E is the same that would appear across the terminals  (I and
         bearing all these aspects in mind.
                                                       h of the original network  when these terminal\ are open circuited.
                                                       and the impedance Z. is that viewed from the same terminals when
         18.6.2 Selecting the protective level of the   all voltage sources within the network  arc short-circuited. Thi\ can
               arrester                                he illustrated by the following example.
                                                         Consider the simple switching circuit of  Figure  18.191~). If we
         For  prospective  voltage  surges,  as  described  in  Table   wish to find the current through  the impedance Z3. on thc closure
         18.1.  which  may  arise  in  the  system  during  normal   of  the snjitch, 5, then:
         operation the protective characteristics of the surge arrester   Voltaee across thij circuit (Zq ) before
                                                                  I
         a  must  be  well  below  the  BIL  of  the equipment at all   closing the switch. ,E
         points. For a minimum protective margin  refer to Table   I=  Eauivalent imnedance.  2. of the remaiiiinz circuit
         18.2. It  is  the  basic  parameter  of  a  surge arrester  that   as seen from this \witch  (Figure 18.19d)
         defines its protective level. This is the voltage that will
         appear across the arrester terminals and thus also across   -   E   I
         the equipment being protected during a current discharge
         on  the occurrence of  a voltage surge. It  should be well
         below the BIL of the equipment under protection. Refer
         to  the  load  diagram  shown  in  Figure  18.17. for  more   -   E
         clarity.                                          z,  z, ‘Z2
                                                             +
           To determine this. consider the simple power circuit   ~  %,  +z,
         diagram of  Figure  18.18(a).  where
                                                       and the voltage  across this circuit
         Z, = surge impedance of the line on which is connected
             the  equipment to be  protected from  the source of
             supply  up to the arrester
   639   640   641   642   643   644   645   646   647   648   649