Page 648 - Industrial Power Engineering and Applications Handbook
P. 648

Surge arresters: application and selection  18/61 3
                                                             be considered as three consecutive discharges for
                                                             all practical purposes. It is, however, seen that in
                                                             service, even two consecutive discharges are rare
                                                             and three may never occur. It is, therefore, sufficient
                                                             to consider two consecutive discharges for selecting
                                                             an  arrester.  The  normal  practice  by  leading
                                                             manufacturers is to specify only the total  energy
          Class
                                                             capability  for  which  their  arresters  would  be
                               \\                 I          suitable during consecutive discharges.
                                                          Apparently a higher level of  V,,,  would  mean a lower
                                                        level of energy absorption by the surge arrester in terms
                                                        of V,.  For an excessive level of W required, it is better to
                                                        select a higher V,.  If it jeopardizes the required protection
                                                        level, then  select another type of  surge arrester with  a
                                                        higher energy capability.
                                                          To determine W from the above it is essential to know
                              VreJ v, -
                 1                         3      3.5   the  system  parameters.  Based  on  system  studies  of
                                                        different voltage systems (transmission  lines particularly)
                            1.95                        many data have been collected. Typical data as suggested
                                                        by IEC 60099-4 are provided in Table 18.6 for a general
                                                        reference. For secondary transmission or primary distri-
         Figure 18.23  Classification of arresters in terms of specific energy   bution  networks  up  to  245 kV  too.  where  a  lightning
         kJ/kV,  versus  V,,,/V,  as in IEC 99-4/1991
                                                        surge forms the basis of selection for the protective level
                                                        (VTe5j of  the arrester, only the  switching surge must  be
                                                        considered to determine energy capability.
         protective  level  of  the  surge arrester, will  conduct  and   Example 18.5 in Section  18.10 illustrates the procedure
         appear as the residual voltage across the arrester in terms   to  determine  the  energy  capability  requirement  of  an
         of its protective level and the rest would be absorbed by   arrester for a particular system. The ultimate selection of
         it.  What  is  absorbed  would  determine  its  absorption
         capability. For a  switching circuit, as shown  in  Figure   an arrester is a compromise between its protective level,
                                                        V,,,  TOV capability and energy absorption capability.
         18.18(a).  this can be theoretically determined by:
                                               ( 1 8. 10)   18.7  Classification of arresters

         where                                          These are classified by their nominal discharge currents
           W = energy absorbed in kWs or kJ (1 W = I  J/s)   I, (8120 s) and surge energy absorption capability during
           V, = prospective switching surge crest voltage (kV)
          V,.,,  = Switching  surge residual  voltage of  the  arrester   a discharge (k . J/k  . V,j. Each discharge current is assigned
                                                        a system voltage according to IEC 60099-4, as noted in
               (kV)                                     Table 18.7. The energy capability of an arrester will vary
                                                        with  the  overvoltage  conditions  of  the  system.  It  is
               N0tp                                     therefore essential to ensure that the arrester chosen has
               As  in  IEC  60099-4.  the  lowest  value  of  Vrcb must  he   sufficient capability to sustain the required system TOV
               considered which occurs at a lower switching surge discharge   and surge conditions during long years of operation. IEC
               current. such as a switching surge, V,,,.  at  1 kA < 2 kA < 3
               hA. etc. Tahles  18.9 and  18.1 I  illustrate this.

           Z, = surge impedance of the affected line    Table 18.6  Typical parameters of a transmission line
            T = travelling  time  of  the  switching  surge from  the
               arrester to the  equipment in  ,us.  The factor 2  is   Line   Line dischurgr
               considered  to  account  for  the  reflection  of  the   discharge  cluss of
                                                               iirrester
                                                        current
               incident switching transient wave at the equipment   (kA 1
               (equation (18.3)). The virtual duration of the surge   ~~   ~
               peak. considered in Table 18.6, also corroborates   I 0   1
               this.                                    IO     2
           PI  = number  of  consecutive  discharges.  The  energy   10   3
               capability of an arrester is its capability to discharge   20   4
               three such switching surges at an interval of 50-   20   S
               60  seconds  each  (IEC  60099-4).  But  since  the   Based on IEC 60099-4
               thermal time constant of ZnO blocks is high (in   'These  are  the  line  discharge  test  values  to  test  an  arrester.  as
               the range of 60- I00 minutes) the time interval of   recommended by IEC and have been considered here lor the purpose
               50-60  seconds does not really  matter, and it may   of  selection  of an arrester. Refcr to Example  18.5.
   643   644   645   646   647   648   649   650   651   652   653