Page 647 - Industrial Power Engineering and Applications Handbook
P. 647

18/61 2  Industrial Power Engineering and Applications Handbook
             -------+
                                                       Note
                                                      A lightning surge protective level is found to be more stringent
                                                      than the switching surge or FOW protective levels. Hence, it
          Protection to be   Surge arrester            is sufficient to check the protective distance requirement for
          near the equipment                           the lightning surge alone.
          and not on the line                           In such cases, care must be taken to reduce the protective
                       -G                              distance, I,  if possible, otherwise equipment with a higher BIL
                                                       may have to  be selected  or  an arrester  with  a  lower  V,,,,
             Figure 18.21  Ideal location of  a surge arrester   considered. Alternatively one may have to provide two arresters
                                                       in parallel, which is also an acceptable practice.

                                                       18.6.3  Required energy capability in kJkV,
                                                       This is the energy the arrester has to absorb while clearing
                                                       a switching surge. It also depends upon the distance of
                                                       the  arrester  from  the  equipment  it  is  protecting,  as
                                                       discussed above. The basic parameters that will determine
                                                       the required energy capability (I'Rt), are current amplitude,
                                                       steepness,  duration  and  number  of  likely  consecutive
                                                       discharges. The energy capability of an arrester depends
                                                       upon the size of the ZnO blocks. By resizing these blocks,
                                                       an arrester of a higher energy capability can be designed.
                                                       Hence, an arrester with a higher kJ/kV, capacity will be
                                                       larger than  one with  a lower KJ/kV,.  ZnO blocks  can
                                                       generally absorb much higher energies at  low currents
                                                       with long durations (i.e. power frequency stresses under
                                                       normal operation) than higher currents for short durations
                                                       (i.e. surge voltage capacitive discharges). To select the
                                                       right type of arrester the energy capability of the arrester
                                                       in  kJ, therefore,  must be determined by  what it has to
                                                       absorb on every discharge. System studies on and past
           Figure 18.22  Effect of  distance on the protective level   experience of  similar other installations can be a good
                                                       guide for the likely number of consecutive discharges an
                                                       arrester may have to perform at a time. Generally, two
                                                       consecutive discharges  are considered to  be  adequate.
                                                       Like other equipment, a surge arrester becomes too heated
        facturers and may be obtained from them for more accurate   too during normal service, even when it is not conducting,
        selection of an arrester.                      due to its continuous charging current, Zzno  (Figure 18.4)
                                                       however  small  the  loss  content. When  the  arrester  is
        Example 18.4                                   conducting, the level of discharge current (I = kV-)  is a
        For the arrester of the previous example,      function of the protective level of the arrester, Vres, and
                                                       the rest of the severity of the voltage surge is absorbed
         V,,,  = 420 kV,                               by the arrester.
          V, = 336 kV                                    The rating of an arrester is therefore defined in terms
         V,,,  = 844 kV for a lightning surge protective margin at 20 kA
             discharge current, from the manufacturer (Table 18.11)   of  its energy  capability  to absorb at least the required
                                                       energy on each discharge and the number of discharges
        It we consider the lightning surge with a steepness of 2000   the arrester may have to perform in quick succession. IEC
        kV/ps, then for a total distance of, say, 8 m from the arrester   60099-4 has prescribed the minimum energy capability
        to the equipment                               that  an  arrester  must  possess,  at  each  discharge.  The
           - 844 ~  2000 x 2 x 8 x                     graphs in Figure 18.23 indicate these levels for different
          s-           0.3                             classes. It  may be noted that an  arrester with  a higher
           = 844 + 107                                 energy  capability level will  mean less strain or risk of
           = 951 kV                                    failure for the arrester, but at a higher cost. A brief procedure
        If we maintain a protective margin of  15% (to be more safe),   to determine the energy level that the arrester may have
        then  the  minimum BIL that the  equipment  under protection   to absorb on each discharge is given below.
        must have                                        Of the three types of surges noted earlier (Table  18.1)
          = 1.15 x 951                                 which the arrester may have to sustain and absorb, the
                                                       switching surge energy would be the maximum that would
          = 1094 kV                                    exist for the longest duration, compared to lightning or
        which is well below the BIL of the equipment (1175 kV) as in   very  steep-fronted  FOWs  (Section  17.3) which  are of
        Table 13.3, list I. One can therefore safely select the arrester   very short duration. Normally, therefore, a switching surge
        with the next higher rated voltage,  V,, at 360 kV and a  V,,,  at   alone is considered for this purpose. During the operation
        904 kV.                                        of a surge arrester, a part of the surge, equivalent to the
   642   643   644   645   646   647   648   649   650   651   652