Page 649 - Industrial Power Engineering and Applications Handbook
P. 649

18/61 4  Industrial  Power Engineering  and Applications  Handbook
       60099-4 has also recommended the line discharge classes   1  They possess  a  low-energy  handling capability  and
       of  arresters, based on the required energy level in k . J/   hence cannot be applied for installations and equipment
       k.Vr and the ratio of  Vr,,/Vr  (Figure  18.23). The energy   that may  be subject to long-duration  (250/2500 ps)
       capability  of  a  normal  arrester  produced  by  leading   switching surges requiring high-energy handling capa-
       manufacturers is generally higher than recommended by   bility. They are, however, suitable to withstand an FOW,
       the IEC for a particular class of arrester. The last column   as this requires a very low energy handling capability
       of Table 18.7 and Figure 18.23 recommend the minimum   which such arresters do possess.
       energy  capability  of  different  classes of  arresters. The   2  They also pose limitations for installations that connect
       class of arrester for a system, particularly for heavy duty,   a number of cables and capacitor banks, as these also
       can be easily chosen with the help of these figures for a   require a higher energy handling capability.
       required level of k.J/k.V,  and a ratio of Vre,/Vr. Arresters   3  They offer a relatively higher VI,,  and may generally
       classes 1 to 5 are regarded as heavy duty and classified   not be suitable for protection of equipment that has a
       as station class by ANSI/IEEE-C62.11. For light duty, a   low BIL. The BIL of a rotating machine or a dry type
       distribution class may be selected to economize on cost.   transformer, for instance, may fall lower than the V,,
       The nominal current, rated voltage, VI, level of protection.   of  such  arresters  and  the  equipment  may  remain
        V,,,,  and energy capability for such arresters are indicated   unprotected.
        in Table 18.7 for a particular manufacturer.   4  Basically  they  are  light-duty  arresters  and  must be
         The subsequent  example  will  provide  a  simple step   installed at locations that are not directly exposed to
        by-step-procedure  to  select an  arrester for a  particular   lightning strikes.
       application >245 kV.
         The application and rating of an arrester is a matter of   These arresters are therefore employed for installations
        system study and systematic insulation coordination, likely   and  equipment  that  are  not  so  critical  as  to  cause  a
        discharge current during a possible lightning discharge   shutdown of the power system. Likely applications may
        at the location of the installation and experience gathered   thus be small distribution networks and equipment such
        from similar installations. Different countries may adopt   as a distribution transformer, feeding residential or small
        different practices, depending upon the stability of their   industrial loads, not directly exposed to the atmosphere
        networks  and the type of  surges that may  arise during   and hence to direct lightning strikes. Such installations
        the  course of  operation.  Hence, only  broad  guidelines   are reasonably shielded, as when installed within a city.
        can be given to choose an arrester. The rest is a decision   In Table 18.8 we provide typical data for an 11 kV surge
        by the application engineer and his experience of power   arrester widely employed for the distribution of power.
        networks.                                     For higher ratings, consult the manufacturer or their data
                                                      sheets. These arresters are normally used for protection
        18.7.1 Application of distribution class surge   against  lightning  surges  rather  than  switching  surges.
              arresters                               Lightning surges discharge only low energy which  such
                                                      arresters can withstand.
        The application of such arresters will be guided by their   With the above in mind,  1.5 and 2.5  kA arresters are
        following basic characteristics:              not  being  used  by  many  power  networks,  presumably


        Table 18.7  Classification of arresters

        Arrester line  discharge    Nnminul  discharge  current
        class                       ut lighming impul~e (8/20/p
        ~~
        As  in ANSI   AF in IEC 6i)Ogd  kA

                                   1  10"                I               Generally more than recommended
                                         up to 400 kV     3 I V,  I 360   as in graphs of Figure  18.23.
                                     IO"
                                     10"
                                     20"   750 kV and above   } 360 < V, 5 750
                                     20"
        Distribution                 5                    up to  132      Not  significant  for the purpose of
        class                                                             arrester  selection
                                   1   2.5'               up to 36
                                                          h
                                      1.5'
        Notes
        "Selection  of  any arrester will depend upon the duty it has to perform (light duty for indoor and heavy duty for outdoor installations)  and
        the required energy absorption capability.
        bYet to be defined by  IEC 60099-4, hut generally for low-voltage systems. Not often  in use for power system applications.
        'The  application of such arresters is noted in Section  18.7.1.
   644   645   646   647   648   649   650   651   652   653   654