Page 844 - Industrial Power Engineering and Applications Handbook
P. 844

24/798 Industrial Power Engineering and Applications Handbook

                                                      its natural loading within  stable limits and hence fulfil
        or   P,,,   = Po x                            the requirement of economical power transfer. The above
                                                      was a theoretical analysis which can provide quite accurate
                                                      results, depending upon the accuracy of the data assumed.
        Since there is no change in the shunt capacitance (X;  = Xc ),   The more  scientific procedure to  conduct this  type  of
              = Po x -\I-                              study, however, would be through a load flow analysis of
                    7
                    11
        :.  P,,,         = 2 Po
                     0.25                              the  steady-state  component  to  study  temporary
                                                       overvoltages  and  transient  analysis  through  a  TNA
        While it is possible that PmaX may be further  raised by a still
        closer compensation, this is not advisable to retain the stability   (transient network analyser) or an EMTP (electromagnetic
        level of the system. The above compensation is even higher   transient programme). TNA is an analogue method while
        than the line length compensation considered earlier and will   EMTP is a digital method of system analysis. For details
        further  improve the electrical  line length.   of system models and procedure to study a system, refer
          Adding shunt capacitors would also reduce Z,  but would   to Miller (1982).
        raise the  electrical  line  length;  hence  it is not considered.   A transmission line may have to operate under different
        Moreover, on EHVs, the charging shunt capacitances, C,,  as   conditions  of  loading  (I, and p.f.) at  different hours of
        such require compensation during light loads or load rejections
        to limitthevoltage rise (regulation) atthe farendorthemidpoint.   the day, and then there may also be seasonal loads. The
        Hence no additional shunt compensation is recommended.   type of reactive compensation therefore must be decided
                                                       for the varying load conditions, so that they  are able to
        Note                                           provide a continuous change in the VAr as demanded. It
        Series  compensation  would  mean  a  low  value  of  Z,  and   is normal practice to have a combination of  series and
        hence a higher system fault level. This needs be kept in mind   shunt reactive  compensations to  suit  all  conditions  of
        while designing the system and selecting the switching devices   loading, some fixed (unswitched) compensators for normal
        or deciding on the protective scheme or its fault setting.   load  conditions and the  remainder  variable,  to  switch
                                                       ON or OFF depending upon the load conditions or load
        Symmetrical lines                              fluctuations.  The  choice  of  different  types  of  reactive
                                                       compensators may be considered on the following basis:
        Equation (24.12) is now modified to
        E, = V,  . COS  0,  + JZ, . I, . sin 0,   (24.13)   1  Shunt  reactors  These  are  provided  as  shown  in

        where                                            Figure 24.23 to compensate for the distributed lumped
        V, =voltage at the midpoint of the line (Figure 24.18)   capacitances, C,,  on EHV networks and also to limit
        0,  = line length or Ferranti effect up to the midpoint of   temporary overvoltages caused during a load rejection,
            the line.                                    followed by a ground fault or a phase fault within the
                                                         prescribed steady-state voltage limits, as noted in Table
                                                         24.3. They absorb reactive power to offset the charging
        The rest  of  the  procedure,  even  the  inferences  drawn   power demand of EHV lines (Table 24.2, column 9).
        above, would remain  the same as for a radial line. The   The selection of a reactor can be made on the basis of
        only  difference  now is that  the  system  would  become   the  duty  it  has  to  perform  and  the  Compensation
        suitable for  twice  the  lengths  of  the  radial  lines  as  a   required. Some of the different types of reactors and
        result of the midpoint effect which doubles the line length.   their characteristics are described in Chapter 27.
                                                           Reactors add to Z, (Z, = JX,,  Xco  ) and hence
        Conclusion
                                                         reduce surge impedance loading (SIL), Po. But most
        A compensated line can transmit much more power than   are the fixed type, depending upon the maximum load
















                                    G                 t                G
                                                  Intermediatory
                                                 switching station
                                SCR - Shunt compensating reactor
                                   Figure 24.23  A  shunt compensated transmission line
   839   840   841   842   843   844   845   846   847   848   849