214  Microprocessor-based and intelligent transmitters

            Table13.6  Outline details of the D series of mass flow sensors
                          Maximum flow  Minimum flow   Zero stability  Pressure rating  Tenzperature  Wetted parts
                          range (Ibimin)  range*  (lbimin)  (Ibimin)   (psi)   rating  (OF)
            Standard pressure
            D6              0-2         0-0.1       0.0002      2600    -400  to 400  316L
            D12             0-1  1      0-0.55      0.0001      1700    -400  to 400  316L
            D25             045         0-2.25      0.005       1900    -400  to 350  316L
            D40             0-90        04.5        0.009       1250    -400  to 350  316L
            D65             0-300       0-15        0.03        2250    -400  to 350  316L
            DlOO            0-1000      0-50        0.10        2250    -400  to 400  316L
            D150            0-2800      0-140       0.30        1500    -400  to 400  316L
            D300            0-7000      0.350       0.70        740     -400  to 400  316L
            D600            0-25000     0-1250      2.5         625     -400  to 400  316L
            Hastelloy  C
            D6              0-2         0-0.1       0.0002      2600    -400  to 400  Hastelloy C
            D12             0-13        0-0.65      0.001       1700    -400  to 400  Hastelloy C
            D25             045         0-2.25      0.005       1900    -400  to 350  Hastelloy C
            D40             0-120       0-6         0.01        1250    -400  to 400  Hastelloy C
            DlOO            0-1000      0-50        0.1         2250    -400  to 400  Hastelloy C
            D150            0-3000      0-150       0.3         1500    -400  to 400  Hastelloy C
            D300            0-7200      0-360       0.7         740     -400  to 400  Hastelloy C
            Lined
            D150            0-2800      0-  140     0.3         1000    32 to 250   Tefzel
            D300            0-7000      0-350       0.7         740     32 to 250   Tefzel
            High pressure
            DH6             0-2         0-0.2       0.0004      5700    -400  to 400  316L
            DH12            0-1  1      0-1.2       0.002       5700    -400  to 400  316L
            DH25            045         0-3         0.0006      4000    -400  to 350  316L
            DH40            0-90        0-10        0.02        2800    -400  to 400  316L
            DHlOO           0-1000      0-150       0.3         5600    -400  to 400  316L
            DH 150          0-2800      0-600       1.2         5600    -400  to 400  316L
            DH300           0-7000      0-2000      4.0         4000    -400  to 400  316L

            *The lowest flow range over which a flowmeter can he spanned.



            Table 13.7  Outline details of  the DL series of  mass flow sensors
                                                         -
                    Maximum flow   Minimum flow   Zero stability   Pressure rating   Temperature   Wetted parts
                    range (lbimin)   range*  (Ibhin)   (lb/min)   (psi)   -   rating  (OF)
            DL65      0-250         0-12.5       0.025        1500     -400  to 350   316L
            DL  100   0-800         040          0.08         900      -400  to 350   316L
            DL200     0-3500        0-175        0.35         740      -400  to 400   3 16L
            *The lowest flow range over which a flowmeter can be spanned



            Table 13.8  Outline details of  the DTseries of mass flow sensors

                   Maximum flow   Minimum $ow   Zero stability   Pressure   Temperature   Wetted parts
                   range (lbimin)   range*  (Ib/min)   (Ibimin)   rating (psi)   rating (OF)
            DL65      0-300         0-15         0.03       900     32 to 800   Hastelloy C/316Li
            DTlOO     0-800         040          0.08       900     32 to 800   Hastelloy C/316L
            DT 1 50   0-1400        0-70         0.14       600     32 to 800   Hastelloy C/316L
            *The lowest flow range over which a flowmeter can be spanned.
            'The  tubing is Hastelloy C and manifold castings and flanges are 316L stainless steel.