Page 109 - Power Electronic Control in Electrical Systems
P. 109

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH003.3D ± 97 ± [82±105/24] 17.11.2001 9:53AM







                                                             Power electronic control in electrical systems 97

                      since E s ˆ V r . This means that the generator at the sending end behaves exactly like
                      the shunt reactor at the receiving end in that both absorb the same amount of
                      reactive power:
                                                       E 2  E 2    1   cos y
                                            Q s ˆ Q r ˆ  s  ˆ  s                         (3:35)
                                                       X    Z 0  sin y
                      The charging current divides equally between the two halves of the line. The voltage
                      profile is symmetrical about the mid-point, and is shown in Figure 3.12 together with
                      the line-current profile. In the left half of the line the charging current is negative;
                      at the mid-point it is zero; and in the right half it is positive. The maximum voltage
                      occurs at the mid-point and is given by equation (3.2) with x ˆ a/2
                                                     y   Z 0  y      E s

                                          V m ˆ V r cos ‡  sin   ˆ                       (3:36)
                                                     2   X    2    cos (y=2)
                      Note that V m is in phase with E s and V r , as is the voltage at all points along the line.
                      For a 300 km line at 50 Hz, y ˆ 18 and with E s ˆ V 0 ˆ 1:0p:u:, the mid-point

                      voltage is 1.0125 p.u. and the reactive power absorbed at each end is 0:158 P 0 . These
                      values should be compared with the receiving-end voltage of 1.05 p.u. and the
                      sending-end reactive-power absorption of Q s ˆ 0:329 P 0 in the absence of the reac-
                      tor. For continuous duty at no-load with a line±line voltage of 500 kV, the rating of
                      the shunt reactor would be 53 MVAr per phase, if Z 0 ˆ 250 
.
                        Equation (3.36) shows that at no-load the line behaves like a symmetrical line as
                      though it were two separate open-circuited lines connected back-to-back and joined
                      at the mid-point. The open-circuit voltage rise on each half is given by equation (3.36)
                      which is consistent with equation (3.21) when P ˆ 0.
                      3.5.1   Multiple shunt reactors along a long line

                      The analysis of Figure 3.12 can be generalized to deal with a line divided into n
                      sections by n  1 shunt reactors spaced at equal intervals, with a shunt reactor at each
                      end. The voltage and current profiles in Figure 3.12 could be reproduced in every
                      section if it were of length a and the terminal conditions were the same. The terminal
                      voltages at the ends of the section shown in Figure 3.12 are equal in magnitude and
                      phase. The currents are equal but opposite in phase. The correct conditions could,
                      therefore, be achieved by connecting shunt reactors of half the reactance given by
                      equation (3.32) at every junction between two sections, as shown in Figure 3.13. The
                      shunt reactors at the ends of the line are each of twice the reactance of the inter-
                      mediate ones. If a is the total length of the composite line, replacing a by a/n in
                      equation (3.32) gives the required reactance of each intermediate reactor


                                                    Z 0   sin (y=n)
                                                X ˆ                                      (3:37)
                                                     2  1   cos (y=n)
                      In Figure 3.13, the sending-end generator supplies no reactive current. In practice it
                      would supply, to a first approximation, only the losses. If the sending-end reactor was
                      removed, the generator would have to absorb the reactive current from the nearest
                      half of the leftmost section. Each intermediate reactor absorbs the line-charging
   104   105   106   107   108   109   110   111   112   113   114