Page 348 - Power Electronics Handbook
P. 348

338   D.C. link  frequency changers

                             is  usually the  case  since  large  reservoir  capacitors  are  connected
                             across the d.c. source, so  that any voltage fluctuation is very small.
                        (VI   The load current is assumed to be continuous, which is again usually
                             the case since most inverter  loads are inductive, and the operating
                             frequency is high enough to give continuous current.
                          With the above assumptions the peak load current IL(pk) can be found by
                        an analysis of the waveform of  Figure 13.50, as in equation (13.23).
                                   1 - exp {- (RIL) [(T/2) - 201)
                          -= IL(W                                                 (13.23)
                          VBIR         1 + exp [-  (RIL) (Tl2)]

                          The r.m.s.  current rating of the devices is obtained by an integral of the
                        currents indicated in Figure 13.50, noting that one arm of the bridge cames
                        a larger current than the other, so that the worst case should be considered.
                        Therefore the rating of  the thyristors can  be  taken  as il over  the time
                        interval (t, - t,), or as the sum of i, over the period (t, - fa) plus i2 over to.
                        The latter gives the worst case and should be the one considered.
                          The values of the thyristor r.m.s. current,   diode r.m.s. current,
                               and  load  r.m.s.  current  IL(rms)  are  given  by  equations  (13.24),
                        (13.27) and (13.28) respectively, the values of  fT0 and P being given by
                        equations (13.25) and (13.26).




                                                                                  (13.24)
                                    LIR    TI2 - 20
                          v$R                LIR    - log P + 2Pexp


                                                                                  (13.25)


                                                                                  (13.26)





                                                                                  (13.27)
                                                                                  (13.28)



                          The above  equations can  be  plotted,  as in  Figures  13.51,  13.52  and
                        13.53, to give the maximum load current, and the rating of  the thyristor
                        and diode. The curves are shown plotted against the fundamental voltage,
                        the value of  the fundamental for any ratio of  2DIT being obtained from
                        Figure 13.34. These plots allow the peak load current and the r.m.s. ratings
                        of  the diode and thyristor to be determined, at any load voltage and r.m.s.
                        load current, and for a given operating frequency.
   343   344   345   346   347   348   349   350   351   352   353